Plan Review Notes
Plan Review Notes For Permit 16061232
Permit Number 16061232
Review Stop M
Sequence Number 2
Notes
Date Text
2016-08-16 14:14:012ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16061232
 8/16/16
  
 1) 2ND REQUEST FOR MINIMUM VENTILATION CALCULATIONS-
 SEE COMMENT #1 FROM THE 1ST REVIEW.
  
 2) THE ENERGYGAUGE CALCULATION SUBMITTAL IS A REDUCED
 SIZE COPY, ALL ENERGY COMPLIANCE DOCUMENTS TO BE
 SUBMITTED SHALL BE ORIGINAL COPIES, AND SHALL BEAR THE
 ORIGINAL SIGNATURES AND REGISTRATION NUMBERS OF THE
 DESIGN PROFESSIONALS- SECTION C103.1.1.1.2 FBC-14
 ENERGY CONSERVATION. ADDITIONALLY, THE BUILDING'S
 OWNER, THE OWNER'S ARCHITECT, OR THE OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER SHALL CERTIFY
 THAT THE BUILDING IS IN COMPLIANCE BY PROVIDING
 SIGNATURES- C103.1.1.2.
  
 3) THE SUBMITTED HVAC LOAD ANALYSIS PREPARED BY KO
 DESIGN IS FOR DULCE PECATTO INC. 2523 DUDLEY DR. IS NOT
 FOR THIS PROPOSED PROJECT AT 4047 OKEECHOBEE RD. PLEASE
 NOTE THAT ONLY THE DESIGN PROFESSIONAL OF RECORD OR THE
 INSTALLING AC CONTRACTOR IS PERMITTED TO DESIGN AC
 PLANS AND SPECIFICATIONS PER SECTION 105.3.1.2 FBC-14
 BUILDING.
  