Plan Review Notes For Permit 16061232 |
Permit Number |
16061232 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2016-08-16 14:14:01 | 2ND REVIEW FBC-2014 MECHANICAL | | PERMIT #16061232 | | 8/16/16 | | | | 1) 2ND REQUEST FOR MINIMUM VENTILATION CALCULATIONS- | | SEE COMMENT #1 FROM THE 1ST REVIEW. | | | | 2) THE ENERGYGAUGE CALCULATION SUBMITTAL IS A REDUCED | | SIZE COPY, ALL ENERGY COMPLIANCE DOCUMENTS TO BE | | SUBMITTED SHALL BE ORIGINAL COPIES, AND SHALL BEAR THE | | ORIGINAL SIGNATURES AND REGISTRATION NUMBERS OF THE | | DESIGN PROFESSIONALS- SECTION C103.1.1.1.2 FBC-14 | | ENERGY CONSERVATION. ADDITIONALLY, THE BUILDING'S | | OWNER, THE OWNER'S ARCHITECT, OR THE OTHER AUTHORIZED | | AGENT LEGALLY DESIGNATED BY THE OWNER SHALL CERTIFY | | THAT THE BUILDING IS IN COMPLIANCE BY PROVIDING | | SIGNATURES- C103.1.1.2. | | | | 3) THE SUBMITTED HVAC LOAD ANALYSIS PREPARED BY KO | | DESIGN IS FOR DULCE PECATTO INC. 2523 DUDLEY DR. IS NOT | | FOR THIS PROPOSED PROJECT AT 4047 OKEECHOBEE RD. PLEASE | | NOTE THAT ONLY THE DESIGN PROFESSIONAL OF RECORD OR THE | | INSTALLING AC CONTRACTOR IS PERMITTED TO DESIGN AC | | PLANS AND SPECIFICATIONS PER SECTION 105.3.1.2 FBC-14 | | BUILDING. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|