2016-06-24 12:15:241ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16061232
 6/24/16
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE:
  
 A) MINIMUM VENTILATION CALCULATIONS FOR ALL ROOMS AND
 SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
  
 B) AC COOLING AND HEATING CALCULATIONS. BECAUSE OF THE
 CHANGE IN USE OF THE SPACE RESULTING IN AN INCREASED
 OCCUPANT LOAD, AND THE ADDITION OF HEAT PRODUCING
 APPLIANCES AND EQUIPMENT, IT NEEDS TO BE VERIFIED THAT
 THE EXISTING AC SYSTEM HAS THE CAPACITY TO HANDLE THE
 INCREASED LOADS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  