2016-06-24 12:15:24 | 1ST REVIEW: FBC 2014 MECHANICAL | | PERMIT #16061232 | | 6/24/16 | | | | 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE | | AND PROVIDE: | | | | A) MINIMUM VENTILATION CALCULATIONS FOR ALL ROOMS AND | | SPACES PER TABLE 403.3 FBC-14 MECHANICAL. | | | | B) AC COOLING AND HEATING CALCULATIONS. BECAUSE OF THE | | CHANGE IN USE OF THE SPACE RESULTING IN AN INCREASED | | OCCUPANT LOAD, AND THE ADDITION OF HEAT PRODUCING | | APPLIANCES AND EQUIPMENT, IT NEEDS TO BE VERIFIED THAT | | THE EXISTING AC SYSTEM HAS THE CAPACITY TO HANDLE THE | | INCREASED LOADS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|