2016-07-05 08:54:21 | INITIAL ELECTRICAL PLAN REVIEW |
| |
| APPLICABLE CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70- 2011 NEC |
| COMMENTS: |
| |
| 1. UPDATE ALL CODE REFERENCES SHOWN ON SHEET E.01 TO |
| SHOW FLORIDA BUILDING CODE 2014 5TH EDITION AND AS |
| STATED ABOVE. |
| 2. GENERAL NOTES- PROVIDE A BLOCK NOTE INDICATING THE |
| REQUIRED SEPARATE PERMITS AND DATA CUT SHEET SUBMITTALS |
| FOR GENERATOR ALL LOW VOLTAGE SYSTEMS TO INCLUDE, PHONE |
| AND DATA, SIGNAGE ETC. A NOTE WILL SUFFICE. |
| 3. PLEASE LABEL RECEPTACLE IN TO BE GFCI PROTECTED PER |
| NEC 210.8B5- IF WITHIN 6FT OF SINK ALL TO BE GFCI. |
| 4. PLEASE LABEL RECEPTACLE IN PREP AREA ALL TO BE GFCI |
| PROTECTED PER NEC 210.8B5- IF WITHIN 6FT OF SINK, ALL |
| TO BE GFCI. |
| 5. ADDRESS FIRE AND MECHANICAL COMMENTS RELATED TO THE |
| ELECTRICAL SCOPE OF WORK. |
| 6. PROVIDE MANUFACTURED DATA SHEETS FOR THE NEW |
| TANKLESS WATER HEATER SHOWN. FBC 107.3.5. ALSO SHOW ON |
| ELECTRICAL PANEL SCHEDULE CALCULATION. |
| 7. ALL NEW DEVICES TO REFLECT CIRCUIT DESIGNATIONS ID. |
| FBC 107.3.5 |
| 8. NOTE SHOWN IS MISLEADING, STATES THAT NO NEW WORK IS |
| BEING PERFORMED BUT NEW DEVICES SHOWN. PLEASE CORRELATE |
| NOTES. |
| 9. FURTHER COMMENTS MAY FOLLOW. PLEASE FEEL FREE TO |
| CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING THIS |
| PROJECT. |
| |
| |