Plan Review Notes
Plan Review Notes For Permit 16061232
Permit Number 16061232
Review Stop E
Sequence Number 1
Notes
Date Text
2016-07-05 08:54:21INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. UPDATE ALL CODE REFERENCES SHOWN ON SHEET E.01 TO
 SHOW FLORIDA BUILDING CODE 2014 5TH EDITION AND AS
 STATED ABOVE.
 2. GENERAL NOTES- PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA CUT SHEET SUBMITTALS
 FOR GENERATOR ALL LOW VOLTAGE SYSTEMS TO INCLUDE, PHONE
 AND DATA, SIGNAGE ETC. A NOTE WILL SUFFICE.
 3. PLEASE LABEL RECEPTACLE IN TO BE GFCI PROTECTED PER
 NEC 210.8B5- IF WITHIN 6FT OF SINK ALL TO BE GFCI.
 4. PLEASE LABEL RECEPTACLE IN PREP AREA ALL TO BE GFCI
 PROTECTED PER NEC 210.8B5- IF WITHIN 6FT OF SINK, ALL
 TO BE GFCI.
 5. ADDRESS FIRE AND MECHANICAL COMMENTS RELATED TO THE
 ELECTRICAL SCOPE OF WORK.
 6. PROVIDE MANUFACTURED DATA SHEETS FOR THE NEW
 TANKLESS WATER HEATER SHOWN. FBC 107.3.5. ALSO SHOW ON
 ELECTRICAL PANEL SCHEDULE CALCULATION.
 7. ALL NEW DEVICES TO REFLECT CIRCUIT DESIGNATIONS ID.
 FBC 107.3.5
 8. NOTE SHOWN IS MISLEADING, STATES THAT NO NEW WORK IS
 BEING PERFORMED BUT NEW DEVICES SHOWN. PLEASE CORRELATE
 NOTES.
 9. FURTHER COMMENTS MAY FOLLOW. PLEASE FEEL FREE TO
 CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING THIS
 PROJECT.
  
  