Plan Review Notes
Plan Review Notes For Permit 16061191
Permit Number 16061191
Review Stop E
Sequence Number 2
Notes
Date Text
2016-08-25 19:18:202ND ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT NAME:
 JOB ADDRESS: 3240 NORTH FLAGLER DR.
 DESCRIPTION: RENOVATION
 MASTER PERMIT: 16061191
  
 BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS.
 ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF
 SUBMITTED CORRECTIONS.
  
 PER THE NEC AND THE FBC-R YOU SHALL PROVIDE THE
 FOLLOWING FOR A SUCCESSFUL ELECTRICAL PLAN REVIEW:
  
 1. NEC 215.5 DIAGRAMS OF FEEDERS. A RISER DIAGRAM
 SHOWING FEEDER DETAILS ALONG WITH RESPECTIVE LOAD CALCS
 SHALL BE PROVIDED. THIS DIAGRAM SHALL INCLUDE CONDUCTOR
 SIZING AND INSULATION TYPE. FURTHERMORE, IT SHALL BE
 SITE SPECIFIC. ALONG WITH THE LOCATION OF THE ELECTRIC
 METER AND THE MDP, YOU SHALL MARK ON THE FLOOR PLAN THE
 LOCATION OF EACH ELECTRICAL LOAD CENTER MENTIONED ON
 THE ABOVE RISER DIAGRAM.
 2. FBC-R3706.2 NEC 408.4(A) REQUIRES THAT YOU PROVIDE A
 PANEL SCHEDULE OR CIRCUIT DIRECTORY LEGIBLY INDICATING
 THE SPECIFIC PURPOSE OF EVERY CIRCUIT. THIS APPLIES TO
 EACH PANEL IDENTIFIED ABOVE.
 3. ITEMS A THRU E BELOW CAN BE ADDRESSED WITH A BLOCK
 NOTE ON THE PLANS.
 A) FBC-RE3902.12/NEC 210.12(B) ARC-FAULT
 CIRCUIT-INTERRUPTER PROTECTION. ALL BRANCH CIRCUITS
 THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE
 OUTLETS INSTALLED IN FAMILY ROOMS, DINING ROOMS, LIVING
 ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS AND SIMILAR ROOMS
 OR AREAS SHALL BE PROTECTED BY A COMBINATION TYPE
 ARC-FAULT CIRCUIT INTERRUPTER INSTALLED TO PROVIDE
 PROTECTION OF THE BRANCH CIRCUIT.
 B) FBC-RE4002.9 NEC 406.9(B) RECEPTACLES IN WET
 LOCATIONS. 15 AND 20 AMPERE, 125 AND 250 VOLT
 RECEPTACLES INSTALLED IN A WET LOCATION SHALL HAVE AN
 ENCLOSURE THAT IS WEATHERPROOF WHETHER OR NOT THE
 ATTACHMENT PLUG CAP IS INSERTED. ALL 15 AND 20 AMPERE,
 125 AND 250 VOLT NONLOCKING RECEPTACLES SHALL BE LISTED
 WEATHER-RESISTANT TYPE ?WR?.
 C) FBC-R4002.14 NEC 406.12 TAMPER-RESISTANT RECEPTACLES
 IN DWELLING UNITS. IN ALL AREAS SPECIFIED IN 210.52,
 ALL 125-VOLT, 15 AND 20 AMPERE RECEPTACLES SHALL BE
 LISTED TAMPER RESISTANT RECEPTACLES.
 D) FBC-ER404.1 LIGHTING EQUIPMENT (MANDATORY). A
 MINIMUM OF 75 PERCENT OF THE LAMPS IN PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY
 LAMPS OR A MINIMUM OF 75 PERCENT OF THE PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH
 EFFICACY LAMPS.
 E) BOTH, THE OUTLETS BELOW TUB AND THE TUB MOTOR SHALL
 BE ACCESSIBLE.
 4. FBC-R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. DURING THIS
 REVIEW I NOTICED MISSING SMOKE DETECTORS AT THE BOTTOM
 OF STAIR 113, HALL 201, AND SUITE LIVING ROOM 218.
 5. FBC-R315.1 CARBON MONOXIDE PROTECTION. EVERY
 SEPARATE BUILDING OR AN ADDITION TO AN EXISTING
 BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
 ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR
 APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER
 FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE
 AS BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL
 CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET (3048
 MM) OF EACH ROOM USED FOR SLEEPING PURPOSES
 6. FBC-RE3901.7 NEC 210.52(E)(3) BALCONIES. BALCONIES,
 DECKS, AND PORCHES THAT ARE ACCESSIBLE FROM INSIDE THE
 DWELLING UNIT SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET
 INSTALLED WITHIN THE PERIMETER OF THE BALCONY, DECK, OR
 PORCH. THE RECEPTACLE SHALL NOT BE LOCATED MORE THAN
 2.0 M (61?2 FT.) ABOVE THE BALCONY, DECK, OR PORCH
 SURFACE.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  