Date |
Text |
2016-06-29 19:00:22 | 1ST ELECTRICAL REVIEW NOTES |
| REVIEWED FOR COMPLIANCE WITH: |
| 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| |
| 1. YOU SHALL MEET MINIMUM PLAN CRITERIA AS FOLLOWS: |
| A) YOU SHALL SUBMIT DEDICATED ELECTRICAL SHEETS TO |
| AVOID UNNECESSARY CLUTTER. |
| B) CLARIFY THE EXTENT OF THE WORK BEING PERFORMED ON |
| THE LIGHTING. YOU NEED TO EXPLAIN IF YOU ARE REPLACING |
| EXISTING FIXTURES WITH UPGRADED LIGHTING IN THE SAME |
| LOCATIONS OR WILL THERE BE ANY REWIRING OF THE CIRCUITS |
| AND INSTALLATION OF NEW SWITCHING AND CONTROLS. THE |
| SAME APPLIES FOR THE RECEPTACLES. |
| 2. PLEASE REFER TO THE 5TH EDITION FBC-EXISTING |
| BUILDING AND DESCRIBE THE LEVEL OF ALTERATION BEING |
| PERFORMED. ALL ELECTRICAL WORK SHALL THEN COMPLY WITH |
| THE REQUIREMENTS OF SUCH. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| THANK YOU, |
| MIKE ALBARRAN |
| ELECTRICAL PLANS EXAMINER |
| PH: 561-805-6746 |
| EMAIL: [email protected] |
| |