2017-02-01 09:20:10 | |
| BUILDING REVIEW APPROVED WITH PROVISO: |
| 1- PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR THE |
| INSTALLATION OF BRICK VENEER, INCLUDING VENEER SUPPORTS |
| AT OPENINGS. ALSO, SPECIFY WEEP-HOLES, ETC. |
| NOTE: PROVIDE COMPLETE DETAILS/ SPECIFICATIONS. DON'T |
| CITE CODE SECTIONS. |
| |
| 2- ENERGY CALCULATIONS WERE REVISED FOR FULL HOUSE |
| COMPLIANCE INSTEAD OF ADDITION ALONE: |
| A) REVISE CEILING INSULATION ITEM #10 TO MATCH PLANS. |
| VENTED AND UNVENTED ROOFS. |
| B) REVISE ROOF MATERIAL SHOWN ON PAGE 2 OF 5 TO MATCH |
| PLANS AND PRODUCT APPROVALS SUBMITTED. |
| C) REVISE CONCRETE BLOCK INSULATION ITEM #9 DOESN'T |
| MATCH PLANS. SEE DETAIL #2 ON SHEET A-10. |
| D) REVISE R-VALUE SHOWN ON THE CEILING INSULATION ON |
| PAGE 3 OF 5 TO MATCH PLANS AND INFORMATION SHOWN ON |
| ITEM #10. |
| E) REVISE DOOR TYPE SPECIFIED ON PAGE 3 OF 5 TO MATCH |
| PLANS AND PRODUCT APPROVALS SUBMITTED. THERE ARE NO |
| INSULATED DOORS. DOORS WITH GLASS NEED TO BE INCLUDED |
| IN THE WINDOWS AREA. |
| F) REVISE WINDOWS OVERHANG DEPTH AND SEPARATION TO |
| MATCH PLANS. |
| G) REVISE NUMBER OF OCCUPANTS ON PAGE 2 OF 5. WHY 20 |
| PEOPLE IN A SINGLE FAMILY RESIDENCE. |
| H) REVISE FLOOR TYPES ON PAGE 2 OF 5. 2ND FLOOR IS NOT |
| ON SLAB ON GRADE. |
| |
| 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.002(33) FOR: |
| A) GARAGE DOORS THAT MEETS ALL THE DESIGN LOADS SHOWN |
| ON SHEET S-6 (POSITIVE AND NEGATIVE). |
| B) DOUBLE EXTERIOR DOORS THAT MEET THE DESIGN PRESSURES |
| SPECIFIED ON SHEET S-6 FOR FAMILY ROOM AREA. |
| |
| 4- ENGINEER OF RECORD TO REVIEW AND APPROVE ABOVE |
| PRODUCT APPROVALS. |