2016-11-01 12:42:321- SPECIFY THE ROOF PITCH FOR EXISTING PORCH LOCATED
 BETWEEN THE GARAGE AND MAIN HOUSE TO VERIFY COMPLIANCE
 WITH THE PROPOSED SHINGLES. ROOF SLOPE MAY BE TOO LOW.
 REPEAT COMMENT. THE ROOF SLOPE WAS NOT SPECIFIED.
 ARCHITECT'S RESPONSE LETTER AND DRAWING A-4 SPECIFIES
 "EXISTING ROOF TO BE REPAIRED AS NEEDED". THIS
 STATEMENT IS TOO GENERAL. WHAT KIND OF REPAIRS ARE
 REQUIRED. REPLACEMENT OF ROOFING?. PROPOSED SHINGLES
 DON'T MATCH EXISTING. IF MORE THAN 25% OF THE SHINGLES
 OF THIS ROOF AREA NEED TO BE REPLACED, THEN ENTIRE ROOF
 SECTION NEEDS TO BE REPLACED. PROPOSED ROOF PRODUCT
 APPROVAL MAY NO BE ALLOWED TO BE INSTALLED BASED ON THE
 ROOF SLOPE. CLEARLY SPECIFY TYPE OF REPAIRS. TOTAL
 SQUARE FOOTAGE, ROOF PITCH, ETC. SEC. 107.2.1 CITY
 AMENDMENTS.
  
  
 APPROVED ROOFING PRODUCT APPROVAL: ENVIROSHAKE NOA
 12-0706.06.