2016-11-08 16:04:34CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 REFER TO SECTION M1602.4 BALANCE RETURN AIR EXCEPTION
 #3 MASTER SUITE. 2014 FBC RESIDENTIAL CODE.
  
 (1) MASTER BEDROOM HAS 525 CFM OF SUPPLY AIR. RETURN
 AIR FROM MASTER BEDROOM ON PLANS IS NOT TO CODE (AS PER
 M1602.4 EXCEPTION #3).
  
 FLORIDA ENERGY CODE FBC 2014
  