Plan Review Notes
Plan Review Notes For Permit 16061174
Permit Number 16061174
Review Stop B
Sequence Number 2
Notes
Date Text
2016-10-27 11:25:22RESIDENTIAL (R3) ADDITION/ALTERATION, SECOND BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
  
 NOTE:
 BUILDING PLAN REVIEW MAY BE PASSED WITH PROVISO.
 CONTRACTOR (OWNER/BUILDER) MAY SUBMIT THE REQUIRED
 INFORMATION AFTER THE PERMIT IS ISSUED BUT BEFORE
 INSPECTIONS TO AVOID CONFLICTS/DELAYS. CONTRACTOR
 (OWNER/BUILDER) TO ADVICE IF PROVISO OPTION IS
 PREFERRED AT THIS TIME.
 REVISION FEES MAY APPLY.
  
  
 1- DETAIL 3/S-1 IS INCOMPLETE: PROVIDE COMPLETE DETAILS
 AND SPECIFICATIONS FOR THE INSTALLATION OF BRICK VENEER
 SHOWING COMPLIANCE WITH SEC. R703.7 FBC-RESIDENTIAL.
 SPECIFY BRICK VENEER SUPPORT AT BOTTOM AND AT OPENINGS.
 ALSO, SPECIFY WEEP-HOLES, ETC.
  
 2- PROVIDE SOIL TEST REPORTS WITH ORIGINAL SEAL &
 SIGNATURES (NO COPIES) AS REQUIRED BY CHAPTER 471 F.S.
  
 3- PLANS TO SPECIFY THE FINISH ELEVATION OF THE
 MECHANICAL AND UTILITY EQUIPMENT SERVICING THE
 BUILDING. NEED AT LEAST 7'-6" ELEVATION. SEC. 94- 546
 CITY CODE.
  
 4- ENERGY CALCULATIONS SUBMITTED:
 A) BUILDER TO COMPLETE THE EPL DISPLAY CARD AS REQUIRED
 BY SEC. R405.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014). REPEAT COMMENT. NOTE: OWNER IS APPLYING FOR THE
 PERMIT AS THE CONTRACTOR. OWNER/BUILDER HAS THE SAME
 RESPONSIBILITIES AS A CONTRACTOR.
  
 B) COMPLETE THE AIR BARRIER AND INSULATION INSPECTION
 CHECKLIST ON TABLE 402.4.1.1 SUBMITTED. SEC. R405.4.3
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). REPEAT
 COMMENT. NOTE: OWNER IS APPLYING FOR THE PERMIT AS THE
 CONTRACTOR. OWNER/BUILDER HAS THE SAME RESPONSIBILITIES
 AS A CONTRACTOR.
  
 C) CEILING INSULATION ITEM #10 DOESN'T MATCH PLANS.
 COORDINATE CEILING INSULATION INSULATION WITH
 ARCHITECTURAL PLANS. SEE WALL SECTION 8-8 ON SHEET A-9.
 SEC. R103.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 NOTE: CLARIFY IF THE 1901 S.F. AREA SHOWN ON ITEM #6 OF
 THE ENERGY CALCULATIONS SUBMITTED IS FOR THE ADDITION
 OF THE FIRST FLOOR ON THE NORTH SIDE AND THE TWO STORY
 ADDITION ON THE EAST SIDE. THE CEILING VENTING AND
 INSULATION VARIES ON BOTH AREAS OF THE HOUSE. SEE
 PLANS. ENERGY CALCULATIONS TO MATCH PLANS. REVISE AS
 REQUIRED.
  
 D) ROOF MATERIAL SHOWN ON PAGE 2 OF 4 DOESN'T MATCH
 PLANS AND PRODUCT APPROVALS SUBMITTED. SEC. R103.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). (REPEAT
 COMMENT. NOT ADDRESSED).
  
 E) COMPLETE ALL THE INFORMATION ON TOP OF FORM,
 INCLUDING BUILDER NAME, PERMIT OFFICE, JURISDICTION
 NUMBER. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014). REPEAT COMMENT. NOTE: OWNER IS APPLYING
 FOR THE PERMIT AS THE CONTRACTOR. OWNER/BUILDER HAS THE
 SAME RESPONSIBILITIES AS A CONTRACTOR.
  
 NEW COMMENTS:
 F) CONCRETE BLOCK INSULATION ITEM #9 DOESN'T MATCH
 PLANS. SEE DETAIL #2 ON SHEET A-10 AND REVISE AS
 REQUIRED. SEC. R103.2 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
  
 G) R-VALUE SHOWN ON THE CEILING INSULATION ON PAGE 3 OF
 4 DOESN'T MATCH PLANS. SEE WALL SECTION 8-8 ON SHEET
 A-9 AND REVISE AS REQUIRED. SEC. R103.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 H) CLEARLY IDENTIFY WHERE ARE THE INSULATED DOORS
 SPECIFIED ON PAGE 3 OF 4?. SEC. R103.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 I) WINDOWS OVERHANG DEPTH AND SEPARATION DON'T MATCH
 PLANS. REVISE AS REQUIRED.SEC. R103.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 NOTE: LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR
 AND SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS
 WILL BE REQUIRED WHEN ENERGY CALCULATIONS ARE NOT USING
 THE SOFTWARE DEFAULT FACTOR FOR GLAZING.
  
 5- SPECIFY THE ROOF PITCH FOR EXISTING PORCH LOCATED
 BETWEEN THE GARAGE AND MAIN HOUSE TO VERIFY COMPLIANCE
 WITH THE PROPOSED SHINGLES. ROOF SLOPE MAY BE TOO LOW.
 REPEAT COMMENT. THE ROOF SLOPE WAS NOT SPECIFIED.
 ARCHITECT'S RESPONSE LETTER AND DRAWING A-4 SPECIFIES
 "EXISTING ROOF TO BE REPAIRED AS NEEDED". THIS
 STATEMENT IS TOO GENERAL. WHAT KIND OF REPAIRS ARE
 REQUIRED. REPLACEMENT OF ROOFING?. PROPOSED SHINGLES
 DON'T MATCH EXISTING. IF MORE THAN 25% OF THE SHINGLES
 OF THIS ROOF AREA NEED TO BE REPLACED, THEN ENTIRE ROOF
 SECTION NEEDS TO BE REPLACED. PROPOSED ROOF PRODUCT
 APPROVAL MAY NO BE ALLOWED TO BE INSTALLED BASED ON THE
 ROOF SLOPE. CLEARLY SPECIFY TYPE OF REPAIRS. TOTAL
 SQUARE FOOTAGE, ROOF PITCH, ETC. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) GARAGE DOORS AS SHOWN ON PLANS. DESIGN PRESSURES
 SHOWN ON FLORIDA PRODUCT APPROVAL FL16546-R6 SUBMITTED
 DON'T MEET THE DESIGN PRESSURES SHOWN ON PLANS ON SHEET
 S-6.
  
 B) EXTERIOR OUTSWING DOORS AS SHOWN ON PLANS. FLORIDA
 PRODUCT APPROVAL FL10196-R3 SUBMITTED DOESN'T MEET THE
 CALCULATED DESIGN PRESSURE ON SHEET S-6 FOR THE DOUBLE
 DOORS.
  
 7- A) ENGINEER OF RECORD TO REVIEW AND APPROVE IN
 WRITING (NOT SIGNING AND SEALING) ABOVE PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 B) ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) THE FLOOD VENT FLORIDA
 PRODUCT APPROVAL FL17588 SUBMITTED. AS REQUIRED BY SEC.
 107.3.4.1 CITY AMENDMENTS.
  
 8- PLANS TO INDICATE THE FINISH FLOOR ELEVATION OF THE
 MAIN HOUSE, GARAGE AND ALL THE EQUIPMENT SERVING THE
 BUILDING. SECTION 107.2.1 CITY AMENDMENTS.
  
 IMPORTANT:
 FLOOD ZONE A5: ELEVATION CERTIFICATES WILL BE REQUIRED
 DURING CONSTRUCTION.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWINGS. DON"T STAPLE OLD DRAWINGS. SUBMITT OLD
 DRAWINGS FOR REFERENCE.
  