2016-08-08 14:41:56 | 1- SPECIFY THE ROOF PITCH FOR EXISTING PORCH LOCATED | | BETWEEN THE GARAGE AND MAIN HOUSE TO VERIFY COMPLIANCE | | WITH THE PROPOSED SHINGLES. ROOF PITCH SEEMS TO BE TOO | | LOW. AND SHINGLES MAY NO BE INSTALLED. LOW SLOPE ROOFS | | REQUIRE A DIFFERENT PRODUCT APPROVAL. SEC. R905.1 | | FBC-RESIDENTIAL. | | | | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | FAC 61G20-3.002(33) FOR: | | A) SHINGLES THAT MEET THE REVISED DESIGN PRESSURES | | CALCULATED ON SHEET. S-6. NOTE: THE DESIGN PRESSURES | | SHOWN ON NOA 12-0514.12 SUBMITTED MAY NOT RESIST THE | | REVISED DESIGN PRESSURES. VERIFY AND RE-SUBMIT. | | | | B) LOW SLOPE ROOF IF REQUIRED BY ITEM #14 ABOVE. | | IDENTIFY SELECTED ASSEMBLY. AND, PROVIDE SIGNED AND | | SEALED RAS 117 CALCULATIONS IF SELECTED ASSEMBLY | | DOESN'T MEET THE CALCULATED DESIGN PRESSURES. | | |
|