Plan Review Notes
Plan Review Notes For Permit 16061174
Permit Number 16061174
Review Stop G
Sequence Number 1
Notes
Date Text
2016-07-25 14:00:171) SHT. P-2 SHOWS THE RANGE AS 122,000 BTU'S BUT SHT.
 P-4 SHOWS THE RANGE AS 65,000 BTU'S. CLARIFY.
 2) SHT.P-4 SHOWS THE TOTAL BTU LOAD AS 321,000 BUT ONLY
 264,000 BTU'S ARE SHOWN ON THE RISER. CLARIFY.
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE GAS
 EQUIPMENT. ALL GAS EQUIPMENT SHALL BE LISTED AND
 LABELED PER 2014 FBCR SEC.G2404.3.
 4) GAS SHALL BE SUBMITTED AS A SEPARATE PERMIT.
  