Plan Review Notes For Permit 16061174 |
Permit Number |
16061174 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-07-25 14:00:17 | 1) SHT. P-2 SHOWS THE RANGE AS 122,000 BTU'S BUT SHT. | | P-4 SHOWS THE RANGE AS 65,000 BTU'S. CLARIFY. | | 2) SHT.P-4 SHOWS THE TOTAL BTU LOAD AS 321,000 BUT ONLY | | 264,000 BTU'S ARE SHOWN ON THE RISER. CLARIFY. | | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE GAS | | EQUIPMENT. ALL GAS EQUIPMENT SHALL BE LISTED AND | | LABELED PER 2014 FBCR SEC.G2404.3. | | 4) GAS SHALL BE SUBMITTED AS A SEPARATE PERMIT. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|