Plan Review Notes
Plan Review Notes For Permit 16061174
Permit Number 16061174
Review Stop B
Sequence Number 1
Notes
Date Text
2016-08-04 19:00:04RESIDENTIAL (R3) ADDITION/ALTERATION, BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 ***NOTE: THERE IS A RED TAG FOR INTERIOR DEMOLITION
 WITHOUT PERMIT. PLEASE SPECIFY HOW MUCH MONEY WAS USED
 FOR DEMOLITION TO PROPERLY ASSESS THE FEES.
  
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEE ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- THE NEW ENTRY DOOR NEEDS TO PROVIDE COMPLIANCE WITH
 THE EGRESS MINIMUM WIDTH REQUIREMENT OF SEC. R311.2
 FBC-RESIDENTIAL, 5TH EDITION (2014). REVISE AS
 REQUIRED.
  
 3- SHEET A-2:
 A) MASTER BEDROOM EGRESS WINDOWS IDENTIFIED AS "E" ON
 PLANS ARE FOR CASEMENT FIXED WINDOWS. FIXED WINDOWS
 DON'T PROVIDE EGRESS. REVISE AS REQUIRED. SEC. 107.2.1
 CITY AMENDMENTS.
 NOTE: SAME APPLIES TO WINDOWS "D" ON BEDROOM #2. REVISE
 AS REQUIRED.
  
 B) SIZE OF WINDOWS SHOWN ON THE WINDOW AND DOORS
 SCHEDULES ARE NOT LEGIBLE. THE NUMBERS ARE TOO SMALL.
 REVISE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. NOTE:
 THIS APPLIES TO SHEET A-3 ALSO.
  
 4- A) SPECIFY ROOF VENTILATION FOR THE ADDITIONS (OR
 SPECIFY IF DESIGNING UNVENTTED ATTICS) SHOWING
 COMPLIANCE WITH SEC. R806 FBC-RESIDENTIAL. PROVIDE
 COMPLETE SPECIFICATIONS. NOTE: COORDINATE WITH THE
 ENERGY CALCULATIONS SUBMITTED. THEY SHOW VENTED ATTIC.
 ALSO, THEY SHOW BLOWN INSULATION. INFORMATION ON PLANS
 AND ENERGY CALCULATIONS NEED TO MATCH). NOTE: SHINGLES
 PRODUCT APPROVAL SUBMITTED REQUIRES VENTILATION.
  
 B) PROVIDE COPY OF ICC EVALUATION REPORT IF FOAM
 INSULATION IS SPECIFIED ON PLANS SEC. R316
 FBC-RESIDENTIAL. NOTE: DESIGNER OF RECORD TO APPROVE
 FOAM INSULATION REPORT PRIOR TO SUBMITTAL TO THIS
 OFFICE.
  
 5- SPECIFY ATTIC ACCESS SIZE AND LOCATION FOR NEW
 FAMILY ROOM WING AREA AND NEW LIVING ROOM WING AREA.
 NOTE: ATTIC ACCESS NEEDS TO BE IN HALLWAY OR READILY
 ACCESSIBLE LOCATION (NOT INSIDE CLOSET. SEE SHEET A-7).
 SEC. R807 FBC-RESIDENTIAL.
  
 6- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE STAIRWAY, RISERS, TREADS, HANDRAILS
 AND GUARDRAILS SHOWING COMPLIANCE WITH TABLE R301.5,
 R311.7 AND SEC. R312.1 OF FBC-RESIDENTIAL. (HANDRAIL
 AND GUARDRAIL SHOP DRAWINGS APPROVED BY THE DESIGNER OF
 RECORD TO BE SUBMITTED LATER PRIOR TO CONSTRUCTION).
  
 7- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 INSTALLATION OF BRICK VENEER SHOWING COMPLIANCE WITH
 SEC. R703.7 FBC-RESIDENTIAL.
  
 8- STRUCTURAL DRAWINGS TO SPECIFY ALL DEAD AND LIVE
 LOADS FOR EACH FLOOR, ROOF AND THE ATTIC LIVE LOADS AS
 REQUIRED BY SEC. R301.1 AND TABLE R301.5
 FBC-RESIDENTIAL. NOTE: SEE FOOTNOTES "B" AND "G" ON
 TABLE R301.5.
  
 9- SHEET S-6:
 A) DESIGN PRESSURES FOR COMPONENTS AND CLADDING SHOWN
 ON FLOOR PLANS FOR EDGE AND INTERIOR WALLS DON'T MATCH
 DESIGN PRESSURES SHOWN ON THE ALLOWABLE WIND LOAD TABLE
 SHOWN ON THE SAME PAGE. REVISE AS REQUIRED. NOTE:
 ACCORDING TO FOOTNOTE ON FIGURE R301.2(7)
 FBC-RESIDENTIAL THE WALL EDGE "A" IS 4'-0" MIN. IN ALL
 CASES. TAKE THIS IN CONSIDERATION WHEN PROVIDING THE
 DESIGN PRESSURES FOR OPENINGS LOCATED IN THE END ZONES.
  
 B) PROVIDE THE DESIGN PRESSURES FOR THE OVERHEAD GARAGE
 DOORS TO VERIFY COMPLIANCE WITH PRODUCT APPROVAL
 SUBMITTED. SEC. R301 FBC-RESIDENTIAL.
  
 C) REVISE THE DESIGN PRESSURES SHOWN ON THE ALLOWABLE
 AND ULTIMATE WIND LOAD INFORMATION TABLES. THE DESIGN
 PRESSURES FOR PERIMETER AND CORNER AREAS ARE TOO LOW
 BASED ON THE BUILDING HEIGHT AND EXPOSURE SHOWN ON
 PLANS. ALSO, CLARIFY WHY THE DESIGN PRESSURES FOR THE
 PERIMETER AND CORNER AREAS ARE EQUAL. DESIGN PRESSURES
 FOR PERIMETER AND CORNER AREAS ARE NOT EQUAL FOR THE
 TYPE OF ROOF SHOWN ON PLANS. REVISE AS REQUIRED. SEC.
 R301. 2.1 FBC-RESIDENTIAL.
  
 10- SEC. R803.2.3.1 REQUIRES 8D RING-SHANK NAILS MIN.
 STRUCTURAL PLANS, SPECIFICATIONS AND DETAILS SPECIFY
 ROOF SHEATHING ATTACHMENT WITH 10D NAILS. PROVIDE
 CALCULATIONS SHOWING THAT 10D NAILS PROVIDE EQUAL OR
 MORE UPLIFT RESISTANCE OR REVISE ALL DETAILS AND
 SPECIFICATIONS SHOWING THE 8D RING SHANK NAILS. SEC.
 107.2.1.3 CITY AMENDMENTS. NOTE: SHINGLES NOA
 12-0514.12 SUBMITTED REQUIRES 8D RING-SHANK NAILS ALSO.
 SEE DECK ATTACHMENT.
  
 11- PROVIDE SOIL TEST REPORT (2 COPIES WITH ORIGINAL
 SEAL/SIGNATURE) AS REQUIRED BY CHAPTER 471 F.S.
  
 12- ACCORDING TO COPY OF ELEVATION CERTIFICATE
 SUBMITTED, THE EQUIPMENT IS LOCATED BELOW THE REQUIRED
 7'-6' FINISH ELEVATION. ALL EQUIPMENT NEEDS TO BE
 RAISED AT 7'-6" MIN. SEC. 94-546 CITY CODE.
  
 13- ENERGY CALCULATIONS SUBMITTED:
 A) BUILDER TO COMPLETE THE EPL DISPLAY CARD AS REQUIRED
 BY SEC. R405.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 B) COMPLETE THE AIR BARRIER AND INSULATION INSPECTION
 CHECKLIST ON TABLE 402.4.1.1 SUBMITTED. SEC. R405.4.3
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 C) COORDINATE ATTIC INSULATION TYPE AND VENTING WITH
 FLOOR PLANS SUBMITTED (PLANS DON'T SHOW BLOWN
 INSULATION). ALSO, COORDINATE ROOF MATERIAL WITH PLANS
 AND PRODUCT APPROVAL SUBMITTED. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 D) COMPLETE ALL THE INFORMATION ON TOP OF FORM,
 INCLUDING BUILDER NAME, PERMIT OFFICE, JURISDICTION
 NUMBER. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
  
 E) REVISE THE ROOF MATERIAL SHOWN ON PAGE 2 OF 4 TO
 MATCH PLANS AND PRODUCT APPROVAL SUBMITTED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 NOTE: LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR
 AND SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS
 WILL BE REQUIRED WHEN ENERGY CALCULATIONS ARE NOT USING
 THE SOFTWARE DEFAULT FACTOR FOR GLAZING.
  
 14- SPECIFY THE ROOF PITCH FOR EXISTING PORCH LOCATED
 BETWEEN THE GARAGE AND MAIN HOUSE TO VERIFY COMPLIANCE
 WITH THE PROPOSED SHINGLES. ROOF PITCH SEEMS TO BE TOO
 LOW. AND SHINGLES MAY NO BE ALLOWED. LOW SLOPE ROOFS
 REQUIRE A DIFFERENT PRODUCT APPROVAL. SEC. R905.1
 FBC-RESIDENTIAL.
  
 15- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) GARAGE DOORS. DESIGN PRESSURES ON FLORIDA PRODUCT
 APPROVAL FL15279-R4 SUBMITTED ARE TOO LOW. NEED DOORS
 THAT MEET THE CALCULATED DESIGN PRESSURES. COORDINATE
 WITH THE DESIGN PRESSURES REQUIRED ON ITEM #9(B) ABOVE.
  
 B) SHINGLES THAT MEET THE REVISED DESIGN PRESSURES
 CALCULATED ON SHEET. S-6. NOTE: THE DESIGN PRESSURES
 SHOWN ON NOA 12-0514.12 SUBMITTED MAY NOT RESIST THE
 REVISED DESIGN PRESSURES. VERIFY AND RE-SUBMIT.
  
 C) LOW SLOPE ROOF IF REQUIRED BY ITEM #14 ABOVE.
 IDENTIFY SELECTED ASSEMBLY. AND, PROVIDE SIGNED AND
 SEALED RAS 117 CALCULATIONS IF SELECTED ASSEMBLY
 DOESN'T MEET THE CALCULATED DESIGN PRESSURES.
  
 D) WINDOW MULLIONS AS SHOWN ON PLANS: (1) THE
 APPLICATION STATUS FOR FL14133-R5 SAYS "APPLIED FOR".
 NEED PRODUCT APPROVAL THAT IS ALREADY APPROVED. OR
 MANUFACTURER MAY APPLY FOR LOCAL PRODUCT APPROVAL.
 (2)PROVIDE DRAWINGS THAT CORRESPOND TO FLORIDA PRODUCT
 APPROVAL FL14133-R5 SUBMITTED. AND, (3)CLEARLY SPECIFY
 SIZE AND LOCATION OF WINDOW MULLIONS TO VERIFY
 COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES.
  
 E) FIXED WINDOWS AS SHOWN ON PLANS : (1) THE
 APPLICATION STATUS FOR FL10188-R7 SAYS "APPLIED FOR".
 NEED PRODUCT APPROVAL THAT IS ALREADY APPROVED. OR
 MANUFACTURER MAY APPLY FOR LOCAL PRODUCT APPROVAL. (2)
 MAKE SURE SELECTED WINDOWS MEET THE REVISED DESIGN
 PRESSURES FOR ALL WINDOWS. (3)PROVIDE DRAWINGS THAT
 CORRESPOND TO FLORIDA PRODUCT APPROVAL FL10188-R7
 SUBMITTED.
  
 F) CASEMENT WINDOWS AS SHOWN ON PLANS : (1) THE
 APPLICATION STATUS FOR FL10197-R4 SAYS "APPLIED FOR".
 NEED PRODUCT APPROVAL THAT IS ALREADY APPROVED. OR
 MANUFACTURER MAY APPLY FOR LOCAL PRODUCT APPROVAL. (2)
 MAKE SURE SELECTED WINDOWS MEET THE REVISED DESIGN
 PRESSURES FOR ALL WINDOWS. (3)PROVIDE DRAWINGS THAT
 CORRESPOND TO FLORIDA PRODUCT APPROVAL FL10197-R-4
 SUBMITTED.
  
 G) EXTERIOR OUTSWING DOORS AS SHOWN ON PLANS. (1)
 PROVIDE DRAWINGS THAT CORRESPOND TO FLORIDA PRODUCT
 APPROVAL FL10196-R3 SUBMITTED. 2) MAKE SURE SELECTED
 DOORS MEET THE REVISED DESIGN PRESSURES FOR ALL DOORS
 SHOWN ON PLANS.
  
 H) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS, SECTIONS AND DETAILS. PROVIDE ONLY THE FLORIDA
 PRODUCT APPROVAL NUMBER AND PAGE SHOWING THE SPECIFIED
 CONNECTOR. OR LIST THE FLORIDA PRODUCT APPROVAL NUMBER
 NEXT TO EACH SPECIFIED CONNECTOR.
  
 16- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 IMPORTANT:
 FLOOD ZONE A5: ELEVATION CERTIFICATES WILL BE REQUIRED
 DURING CONSTRUCTION.
  
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWINGS. DON"T STAPLE OLD DRAWINGS. SUBMITT OLD
 DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  