2016-06-27 17:02:04FLORIDA BUILDING CODE 5TH EDITION (2014) MECHANICAL
  
 606.2.1 RETURN AIR SYSTEMS.
 SMOKE DETECTORS SHALL BE INSTALLED IN RETURN AIR
 SYSTEMS WITH A DESIGN CAPACITY GREATER THAN 2,000 CFM
 (0.9 M3/S) IN THE RETURN AIR DUCT OR PLENUM UPSTREAM OF
 ANY FILTERS, EXHAUST AIR CONNECTIONS, OUTDOOR AIR
 CONNECTIONS, OR DECONTAMINATION EQUIPMENT AND
 APPLIANCES.
  
 606.2.2 COMMON SUPPLY AND RETURN AIR SYSTEMS.
 WHERE MULTIPLE AIR-HANDLING SYSTEMS SHARE COMMON SUPPLY
 OR RETURN AIR DUCTS OR PLENUMS WITH A COMBINED DESIGN
 CAPACITY GREATER THAN 2,000 CFM (0.9 M3/S), THE RETURN
 AIR SYSTEM SHALL BE PROVIDED WITH SMOKE DETECTORS IN
 ACCORDANCE WITH SECTION 606.2.1.
  
 606.2.3 RETURN AIR RISERS.
 WHERE RETURN AIR RISERS SERVE TWO OR MORE STORIES AND
 SERVE ANY PORTION OF A RETURN AIR SYSTEM HAVING A
 DESIGN CAPACITY GREATER THAN 15,000 CFM (7.1 M3/S),
 SMOKE DETECTORS SHALL BE INSTALLED AT EACH STORY. SUCH
 SMOKE DETECTORS SHALL BE LOCATED UPSTREAM OF THE
 CONNECTION BETWEEN THE RETURN AIR RISER AND ANY AIR
 DUCTS OR PLENUMS.
  
 PROVIDE EQUIPMENT SCHEDULE FOR ALL (4) RTU.
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER