Plan Review Notes For Permit 16061164 |
Permit Number |
16061164 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-06-27 17:02:04 | FLORIDA BUILDING CODE 5TH EDITION (2014) MECHANICAL | | | | 606.2.1 RETURN AIR SYSTEMS. | | SMOKE DETECTORS SHALL BE INSTALLED IN RETURN AIR | | SYSTEMS WITH A DESIGN CAPACITY GREATER THAN 2,000 CFM | | (0.9 M3/S) IN THE RETURN AIR DUCT OR PLENUM UPSTREAM OF | | ANY FILTERS, EXHAUST AIR CONNECTIONS, OUTDOOR AIR | | CONNECTIONS, OR DECONTAMINATION EQUIPMENT AND | | APPLIANCES. | | | | 606.2.2 COMMON SUPPLY AND RETURN AIR SYSTEMS. | | WHERE MULTIPLE AIR-HANDLING SYSTEMS SHARE COMMON SUPPLY | | OR RETURN AIR DUCTS OR PLENUMS WITH A COMBINED DESIGN | | CAPACITY GREATER THAN 2,000 CFM (0.9 M3/S), THE RETURN | | AIR SYSTEM SHALL BE PROVIDED WITH SMOKE DETECTORS IN | | ACCORDANCE WITH SECTION 606.2.1. | | | | 606.2.3 RETURN AIR RISERS. | | WHERE RETURN AIR RISERS SERVE TWO OR MORE STORIES AND | | SERVE ANY PORTION OF A RETURN AIR SYSTEM HAVING A | | DESIGN CAPACITY GREATER THAN 15,000 CFM (7.1 M3/S), | | SMOKE DETECTORS SHALL BE INSTALLED AT EACH STORY. SUCH | | SMOKE DETECTORS SHALL BE LOCATED UPSTREAM OF THE | | CONNECTION BETWEEN THE RETURN AIR RISER AND ANY AIR | | DUCTS OR PLENUMS. | | | | PROVIDE EQUIPMENT SCHEDULE FOR ALL (4) RTU. | | | | JORGE VALIDO | | WPB MECHANICAL INSPECTOR/PLANS EXAMINER | | [email protected] | | 561-805-6716 | | | | | | |
|