Plan Review Notes For Permit 16061121 |
Permit Number |
16061121 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-07-07 09:33:19 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | - FINAL APPROVAL DEPENDS ON ZONING REVIEW COMMENTS | | | | - C405.2.4 EXTERIOR LIGHTING CONTROLS. LIGHTING NOT | | DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE | | CONTROLLED BY EITHER A COMBINATION OF A PHOTOSENSOR AND | | A TIME SWITCH, OR AN ASTRONOMICAL TIME SWITCH. LIGHTING | | DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE | | CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR | | PHOTOSENSOR. | | ALL TIME SWITCHES SHALL BE CAPABLE OF RETAINING | | PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER | | FOR A PERIOD OF AT LEAST 10 HOURS. ADD A NOTE ON THE | | PLANS TO COMPLY. |
|