Plan Review Notes
Plan Review Notes For Permit 16061119
Permit Number 16061119
Review Stop E
Sequence Number 1
Notes
Date Text
2016-07-07 09:18:28REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 - FINAL APPROVAL DEPENDS ON CITY ZONING COMMENTS,
 PROVIDE ELECTRICAL INFORMATION ON THE PLANS FOR THE
 INTENDED SIGN.
  
 - NEC 600.5 A DEDICATED 20 AMP CIRCUIT THAT SERVES NO
 OTHER LOAD SHALL FEED THE SIGN, IF EXISTING PLEASE MARK
 ON PLANS !
  
 - NEC 600.6 A DISCONNECT IS REQUIRED WITHIN SIGHT OF
 THE SIGN INTERGRATED OR ADJACENT IF OUT OF LINE OF
 SIGHT THE DISCONNECTING MEANS SHALL BE CAPABLE OF BEING
 LOCK IN THE OPEN POSITION WITH PROPER LABELING
 IDENTIFICATION.
  
 - ALL GROUNDING AND BONDING SHALL COMPLY WITH NEC
 600.7(A)(B). GENERAL COMMENT.
  
 - C405.2.4 EXTERIOR LIGHTING CONTROLS. LIGHTING NOT
 DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE
 CONTROLLED BY EITHER A COMBINATION OF A PHOTOSENSOR AND
 A TIME SWITCH, OR AN ASTRONOMICAL TIME SWITCH. LIGHTING
 DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE
 CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR
 PHOTOSENSOR.
 ALL TIME SWITCHES SHALL BE CAPABLE OF RETAINING
 PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER
 FOR A PERIOD OF AT LEAST 10 HOURS.