Plan Review Notes For Permit 16061119 |
Permit Number |
16061119 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-07-07 09:18:28 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | | | - FINAL APPROVAL DEPENDS ON CITY ZONING COMMENTS, | | PROVIDE ELECTRICAL INFORMATION ON THE PLANS FOR THE | | INTENDED SIGN. | | | | - NEC 600.5 A DEDICATED 20 AMP CIRCUIT THAT SERVES NO | | OTHER LOAD SHALL FEED THE SIGN, IF EXISTING PLEASE MARK | | ON PLANS ! | | | | - NEC 600.6 A DISCONNECT IS REQUIRED WITHIN SIGHT OF | | THE SIGN INTERGRATED OR ADJACENT IF OUT OF LINE OF | | SIGHT THE DISCONNECTING MEANS SHALL BE CAPABLE OF BEING | | LOCK IN THE OPEN POSITION WITH PROPER LABELING | | IDENTIFICATION. | | | | - ALL GROUNDING AND BONDING SHALL COMPLY WITH NEC | | 600.7(A)(B). GENERAL COMMENT. | | | | - C405.2.4 EXTERIOR LIGHTING CONTROLS. LIGHTING NOT | | DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE | | CONTROLLED BY EITHER A COMBINATION OF A PHOTOSENSOR AND | | A TIME SWITCH, OR AN ASTRONOMICAL TIME SWITCH. LIGHTING | | DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE | | CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR | | PHOTOSENSOR. | | ALL TIME SWITCHES SHALL BE CAPABLE OF RETAINING | | PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER | | FOR A PERIOD OF AT LEAST 10 HOURS. |
|