Plan Review Notes For Permit 16061090 |
Permit Number |
16061090 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-08-09 17:33:32 | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA | | BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION | | | | 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1 | | INFORMATION ON CONSTRUCTION DOCUMENTS | | | | REVIEW ALL DUCT SIZES AND CFM QUANTITIES. | | CHECK BED ROOM #8. | | 6" DUCT @ .1% FRICTION LOST CANNOT PROVIDE 254 CFM. | | CHECK BATHROOM ON 2ND FLOOR. 185 CFM IS TOO MUCH AIR | | PER CFM PER SQFT RATIO (0.817) GIVEN. | | | | CHECK ALL BEDROOMS. | | CFM PER SQFT 0.817 DOES NOT MEET THE PLANS SCALE SQFT | | OF THE BEDROOMS. PROVIDE PROPER SCALE OR MAKE | | CORRECTIONS TO CFM AND DUCT SIZES. | | | | FLORIDA ENERGY CODE FBC 2014 | | | | PROVIDE AHRI FOR EQUIPMENT INSTALLED. | | | | JORGE VALIDO | | WPB MECHANICAL INSPECTOR/PLANS EXAMINER | | [email protected] | | 561-805-6716 | | | | |
|