2016-08-09 17:33:32CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 REVIEW ALL DUCT SIZES AND CFM QUANTITIES.
 CHECK BED ROOM #8.
 6" DUCT @ .1% FRICTION LOST CANNOT PROVIDE 254 CFM.
 CHECK BATHROOM ON 2ND FLOOR. 185 CFM IS TOO MUCH AIR
 PER CFM PER SQFT RATIO (0.817) GIVEN.
  
 CHECK ALL BEDROOMS.
 CFM PER SQFT 0.817 DOES NOT MEET THE PLANS SCALE SQFT
 OF THE BEDROOMS. PROVIDE PROPER SCALE OR MAKE
 CORRECTIONS TO CFM AND DUCT SIZES.
  
 FLORIDA ENERGY CODE FBC 2014
  
 PROVIDE AHRI FOR EQUIPMENT INSTALLED.
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER