Plan Review Notes
Plan Review Notes For Permit 16061084
Permit Number 16061084
Review Stop B
Sequence Number 3
Notes
Date Text
2016-08-08 11:30:23****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PROVIDE A SIGNED AND SEALED LETTER FROM THE ENGINEER
 OF RECORD WHICH ACKNOWLEDGES THE CHANGE IN DESIGN
 (CABLE GROUPINGS ELIMINATED AT LEVELS 8, 9, 10) AND THE
 STATEMENT MADE REGARDING SUFFICIENT CAPACITY (REFER TO
 SHOP REVIEW BY CORDELL VAN NOSTRAND), FAC61G15.
  
 2. CONTRACTOR IS RESPONSIBLE FOR PROVIDING THREE
 COLLATED COMPLETE SETS. THE FIRST SUBMITTAL WAS FOR
 POST TENSION DELEGATED ENGINEERING, FLOORS 8-20, AND
 INCLUDED CALCULATIONS. THE SECOND SUBMITTAL INCLUDES
 REVISED DRAWINGS MARKED 8-20, BUT ALSO INCLUDES A
 LETTER WHICH STATES THAT THREE CABLE GROUPINGS
 (109-111) WERE MISSED ON FLOORS 8-10. THE PREVIOUS
 SUBMITTAL WAS MARKED "VOID" AND THE CURRENT SUBMITTAL
 TITLE BLOCK STATES THAT THIS IS FOR FLOORS 8-20, AND
 CALCS FOR 109-11 INCLUDED.
  
 IT APPEARS THAT THE POST TENSION ENGINEERING AND CALCS
 SHOULD BE REVISED; ONE DRAWING AND CALCS FOR FLOORS
 8-10, AND ANOTHER SEPARATE SUBMITTAL WHICH INCLUDES
 DRAWINGS AND CALCS FOR FLOORS 11-20. PLEASE REVISE
 ACCORDINGLY OR CONTACT ME TO DISCUSS.
  