Plan Review Notes For Permit 16060963 |
Permit Number |
16060963 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-06-27 09:45:46 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | | | - FBC 107.2.1 PLEASE CLEARLY IDENTIFY THE SCOPE OF | | WORK. THE APPLICATION SHOWS "KITCHEN REMODEL", HOWEVER | | WORK IS BEING DONE IN THE BATHROOMS AS WELL ? HAVE THE | | PLANS SIGNED AND DATED BY THE DESIGNER RESPONSIBLE FOR | | THE DRAWING. | | | | - IF THE KITCHEN AND BATHROOMS ARE BEING REMODELED AN | | ELECTRICAL SUB PERMIT WILL BE REQUIRED. THE PLANS SHALL | | INCLUDE FBC R SECTIONS E3901.4 KITCHEN COUNTERTOP SPACE | | REQUIREMENTS & E3901.6 BATHROOM RECEPTACLE OUTLETS. | | | | - SHOW LOCATIONS OF OUTLETS ON THE FLOOR PLAN INCLUDE | | GFCI PROTECTION FOR E3902.1 BATHROOMS, E3902.6 | | KITCHENS. |
|