2016-06-17 04:38:191) SUBMIT TWO COPIES OF THE TANKLESS WATER HEATER
 SPECS.WPB AMEND. TO FBC SEC. 107.1.
 2) IS THIS TANKLESS WATER HEATER REPLACING AN EXISTING
 TANKLESS WATER HEATER OR IS IT REPLACING A STORAGE TANK
 TYPE WATER HEATER OR IS IT BEING ADDED TO THEEXISTING
 HOT WATER SYSTEM? INDICATE ON THE APPLICATION IN THE
 DESCRIPTION OF WORK.
 3) SUBMIT A FLOOR PLAN SHOWING THE LOCATION OF THE NEW
 TANKLESS WATER HEATER.
 4) IS THIS TANKLESS WATER BEING ADDED TO AN EXISTING
 GAS SYSTEM? SUBMIT A COMPLETE GAS RISER WITH ALL PIPE
 SIZES, TYPE OF PIPE, THE DEVELOPED LENGTH TO THE
 FURTHEST GAS OUTLET, THE BTU LOAD OF EACH APPLIANCE,
 THE PSI OF THE SYSTEM, TYPE OF GAS AND THE TOTAL BTU
 LOAD ON THE SYSTEM.DO THE SAME IF IT IS A NEW GAS
 SYSTEM
 5) TYPE OF GAS (LP OR NATURAL).
 6) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
 7) AN ADDITIONAL APPLICATION IS REQUIRED TO INSTALL THE
 WATER LINES FOR THE HEATER.
  