2016-06-21 10:00:22 | 1ST REVIEW: FBC 2014 MECHANICAL | | PERMIT #16060927 | | 6/20/17 | | | | 1) THE AIR SUPPLIED TO THE LAB SUPPIES ROOM HAS A | | RECIRCULATION LIMIT OF 10% PER TABLE 403.3 FBC-14 | | FOOTNOTE G. IT APPEARS FROM THE DRAWING THAT AN AMOUNT | | EXCEEDING 10% WILL BE RETURNED AND RECIRCULATED. THE | | PLAN IS ALSO INDICATING THE REQUIRED EXHAUST FAN IN THE | | ROOM HOWEVER THERE ARE NO DETAILS FOR THE FAN, OR | | EXHAUST VENTIATION CALCULATIONS FOR SIZING THE FAN. | | | | 2) PLEASE INDICATE THE CONTROLS OPERATION SEQUENCE FOR | | EF-2. WILL THE FAN(S) BE LINKED TO THE AC SYSTEM? | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|