2016-06-16 10:56:50 | ROOF RE-COVER BUILDING REVIEW COMMENTS. |
| CODE: FBC 5TH EDITION (2014). |
| |
| 1- ITEM #7 OF THE CONTRACTOR'S SCOPE OF WORK SUBMITTED |
| SAYS: "FURNISH AND INSTALL ONE (1) NEW HATCH AND |
| LADDER-UP SAFETY POST". NEED TO PROVIDE COMPLETE |
| STRUCTURAL FRAMING DETAILS AND SPECIFICATIONS ALONG |
| WITH HATCH PRODUCT APPROVAL UNDER A SEPARATE PERMIT. |
| ROOFING CONTRACTOR CAN NOT DO THIS WORK UNLESS THE |
| ROOFING CONTRACTOR HAS A LICENSE TO DO STRUCTURAL WORK. |
| SEC. 489.113 FLORIDA STATUTES. |
| |
| 2- ITEM #8 OF THE CONTRACTOR'S SCOPE OF WORK SUBMITTED |
| SAYS: "REMOVE AND RE-INSTALL MECHANICAL/ELECTRICAL |
| LINES AS THEY CURRENTLY EXIST" . NEED TO PROVIDE |
| COMPLETE INFORMATION UNDER A SEPARATE PERMIT. ROOFING |
| CONTRACTOR CAN NOT DO THIS WORK UNLESS THE ROOFING |
| CONTRACTOR HAS A LICENSE TO DO SPECIFIED WORK. SEC. |
| 489.113 FLORIDA STATUTES. |
| |
| 3- ITEM #9 OF THE CONTRACTOR'S SCOPE OF WORK SUBMITTED |
| SAYS: "BRING ALL EXISTING HVAC EQUIPMENT UP TO CURRENT |
| FBC REQUIREMENTS". NEED TO PROVIDE COMPLETE INFORMATION |
| UNDER A SEPARATE PERMIT. ROOFING CONTRACTOR CAN NOT DO |
| THIS WORK UNLESS THE ROOFING CONTRACTOR HAS A LICENSE |
| TO DO SPECIFIED WORK. SEC. 489.113 FLORIDA STATUTES. |
| |
| *** NOTE: THE ROOFING PERMIT MAY BE ISSUED WITH A |
| PROVISO. PROVIDE MEANS THAT SEPARATE PERMITS WILL BE |
| OBTAINED PRIOR TO INSPECTIONS TO AVOID CONFLICTS OR |
| DELAYS. CONTRACTOR TO ADVISE HOW ADRESSING THE ABOVE |
| COMMENTS. |
| |