2016-06-16 18:59:19RESIDENTIAL (R3) ENTRY DOOR REPLACEMENT, BUILDING
 REVIEW COMMENTS.
 CODE: FBC 5TH EDITION(2014).
  
 1- ACCORDING TO CITY RECORDS THE ENTRY DOOR SIZE IS
 3'-0 X 6'-8". THE PROPOSED SIZE IS 2'-10". THE SIZE OF
 THE DOOR CAN NOT BE REDUCED. SEC. 701.2 OF FBC-EXISTING
 BUILDING, 5TH EDITION (2014). REVISE AS REQUIRED.
  
 2- ACCORDING TO SEC. R301.2.1.4 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014) THIS BUILDING IS LOCATED IN EXPOSURE "C"
 NOT EXPOSURE "B" AS SHOWN ON WIND-LOADS TABLE
 SUBMITTED. ALSO, THE DOOR IS LOCATED IN ZONE 5 NOT ZONE
 4. THE DOOR PRODUCT APPROVAL FL17184-R3 SUBMITTED
 DOESN'T MEET THE DESIGN PRESSURES SHOWN ON THE WIND-
 LOAD TABLE SUBMITTED. PROVIDE PRODUCT APPROVAL THAT
 MEETS THE CALCULATED DESIGN PRESSURES.
  