Plan Review Notes For Permit 16060879 |
Permit Number |
16060879 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-06-16 18:59:19 | RESIDENTIAL (R3) ENTRY DOOR REPLACEMENT, BUILDING | | REVIEW COMMENTS. | | CODE: FBC 5TH EDITION(2014). | | | | 1- ACCORDING TO CITY RECORDS THE ENTRY DOOR SIZE IS | | 3'-0 X 6'-8". THE PROPOSED SIZE IS 2'-10". THE SIZE OF | | THE DOOR CAN NOT BE REDUCED. SEC. 701.2 OF FBC-EXISTING | | BUILDING, 5TH EDITION (2014). REVISE AS REQUIRED. | | | | 2- ACCORDING TO SEC. R301.2.1.4 OF FBC-RESIDENTIAL, 5TH | | EDITION (2014) THIS BUILDING IS LOCATED IN EXPOSURE "C" | | NOT EXPOSURE "B" AS SHOWN ON WIND-LOADS TABLE | | SUBMITTED. ALSO, THE DOOR IS LOCATED IN ZONE 5 NOT ZONE | | 4. THE DOOR PRODUCT APPROVAL FL17184-R3 SUBMITTED | | DOESN'T MEET THE DESIGN PRESSURES SHOWN ON THE WIND- | | LOAD TABLE SUBMITTED. PROVIDE PRODUCT APPROVAL THAT | | MEETS THE CALCULATED DESIGN PRESSURES. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] |
|