2016-06-14 11:13:12 | 06/14/16: PER MEETING WITH STEVE MALLEK (ROOFING |
| CONTRACTOR), THE ROOFING SUB-PERMIT WAS ISSUED TO ALLOW |
| FOR CONCRETE ROOF TILE DRY-IN INSPECTION . FOLLOWING |
| COMMENTS NEED TO BE ADDRESSED BEFORE INSPECTIONS TO |
| AVOID CONFLICTS/DELAYS. THIS CHECKLIST WAS E-MAILED TO |
| GENERAL CONTRACTOR AND ROOFING CONTRACTOR. JG. |
| |
| |
| RESIDENTIAL (R3) REVISION ADDRESSING BUILDING PROVISO, |
| SECOND BUILDING REVIEW CHECKLIST. |
| CODE: FBC 5TH EDITION (2014). |
| |
| ORIGINAL COMMENT: |
| 1- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR: |
| A) FLAT ROOF. AND, IDENTIFY APPROVED ASSEMBLY TO BE |
| INSTALLED. NOTE: SIGNED & SEALED RAS 117 CALCULATIONS |
| WILL BE REQUIRED IF THE ASSEMBLY DOESN'T MEET THE |
| DESIGN PRESSURES OF SEC. R301. |
| |
| RESPONSE: NOT ADDRESSED YET. NEED TO PROVIDE. THIS IS |
| FOR THE FLAT DECK ABOVE THE NEW TWO STORY STAIRWAY |
| TOWER. SEE PLANS. |
| |
| ORIGINAL COMMENT: |
| B) SECOND FLOOR DECK UNDERLAYMENT DESIGNED TO RECEIVED |
| TILE AS SPECIFIED ON PLANS. AND, IDENTIFY APPROVED |
| ASSEMBLY TO BE INSTALLED. NOTE: SIGNED & SEALED RAS 117 |
| CALCULATIONS WILL BE REQUIRED IF THE ASSEMBLY DOESN'T |
| MEET THE DESIGN PRESSURES OF SEC. R301. |
| SEAL-O-FLEX NOA 15-0406.03 SUBMITTED IS FOR INSULATED |
| ASSEMBLIES. ARCHITECTURAL PLANS DON'T SPECIFY INSULATED |
| ASSEMBLIES. |
| |
| RESPONSE: FLORIDA PRODUCT APPROVAL FL2144-R6 SUBMITTED |
| CAN NOT BE USED BECAUSE OF THE FOLLOWING: (1)IT'S NOT |
| DESIGNED TO RECEIVED TILE AS SHOWN ON ARCHITECTURAL |
| PLANS. SEE PRODUCT DESCRIPTION TABLE ON PAGE 1 OF 3 OF |
| FL2144-R6 SUBMITTED FOR THE ROOF COATINGS ALLOWED FOR |
| THIS TYPE OF LIQUID APPLIED MEMBRANE. NONE OF THEM |
| DESCRIBE TILE AS THE ROOF COATING. (2) SELECTED |
| ASSEMBLIES W-A-1 AND W-A-2 ON PAGE 13 OF 14 OF |
| FL2144-R6 ARE FOR FULLY ADHERED MEMBRANES WITH MAXIMUM |
| DESIGN PRESSURES OF -60PSF AND -85PSF RESPECTIVELY. |
| LIMITATION #9 ON PAGE 3 OF 3 DOESN'T ALLOW DESIGN |
| PRESSURES AUGMENTATION. ACCORDING TO SEC. R301 OF |
| FBC-RESIDENTIAL, 5TH EDITION (2014) THE DESIGN |
| PRESSURES FOR THE PERIMETER AND CORNER AREAS ARE |
| HIGHER. THEREFORE THEY CAN NOT BE USED. NEED TO PROVIDE |
| PRODUCT APPROVAL THAT IS DESIGNED TO RECEIVE TILE AS |
| SPECIFIED ON PLANS. AND, NEED RAS 117 CALCULATIONS IF |
| THE SELECTED ASSEMBLY ALLOWS IT. |
| |
| ORIGINAL COMMENT: |
| C) INSWING ENTRY DOOR SIZE DOOR AS SHOWN ON PLANS AT |
| THE STAIR HALL. PROVIDE COMPLETE FLORIDA PRODUCT |
| APPROVAL COVER PAGES AND THE CORRESPONDING DRAWINGS. |
| RESPONSE: NOT ADDRESSED. |
| |
| 2- DESIGNER OF RECORD TO APPROVE IN WRITING ALL PRODUCT |
| APPROVALS. |
| |
| |
| THE FOLLOWING ARE COMMENTS ARE FOR THE SUBMITTED |
| INFORMATION: |
| ORIGINAL COMMENT: |
| (1) CONCRETE ROOF TILE NOA 12-0222.03 SUBMITTED NOW WAS |
| ALREADY SUBMITTED AND APPROVED WITH THE ORIGINAL PERMIT |
| SET. CLARIFY WHY SUBMITTING PRODUCT APPROVAL AGAIN. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| RESPONSE: OK. APPROVED PRODUCT APPROVAL SHOULD BE ON |
| SITE ALONG WITH THE REST OF THE APPROVED PRODUCT |
| APPROVALS. |
| |
| |
| ORIGINAL COMMENT: |
| (2) ARCHITECTURAL PLANS SPECIFY "CEMENT TILE ON 90# |
| FELT HOT MOPPED ON 30# FELT TIN TAGGED AT 6" EDGES AND |
| 12" FIELD O.C." THIS SUBMITTAL INCLUDES BORAL TILESEAL |
| SELF-ADHERING UNDERLAYMENT AND TILE BOND ROOF TILE |
| ADHESIVE. IF THERE IS A CHANGE IN THE ROOF TILE |
| FASTENING AND UNDERLAYMENT METHOD, THEN REVISE |
| ARCHITECTURAL PLANS ACCORDINGLY. SEC. 107.2.1.2 CITY |
| AMENDMENTS. |
| RESPONSE: THIS ITEM STILL NEEDS TO BE ADDRESSED. |
| |
| (3) DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 |
| CITY AMENDMENTS. |
| |
| ORIGINAL COMMENT: |
| NOTE: THERE WAS A ROOFING APPLICATION INSERTED IN THE |
| PACKAGE SUBMITTED. ROOFING SUB-PERMIT WILL BE PROCESSED |
| WHEN PENDING ROOFING ITEMS ARE ADDRESSED. |
| RESPONSE: PER MEETING WITH STEVE MALLEK (CJM ROOFING), |
| THE ROOFING SUB-PERMIT WAS ISSUED TO ALLOW FOR CONCRETE |
| TILE DRY-IN INSPECTIONS. ALL THE PENDING ITEMS NEED TO |
| BE ADDRESSED BEFORE INSPECTIONS TO AVOID |
| CONFLICTS/DELAYS. PLEASE USE THIS REVISION NUMBER |
| (16060273) FOR SUBMITTAL TO KEEP TRACK OF ALL THE |
| PENDING ITEMS. |
| |
| ***NOTE: |
| NUMBER OF PAGES WILL BE COORDINATED WHEN ADDRESSING |
| COMMENTS. NEW PRODUCT APPROVALS (NOT PART OF THE |
| ORIGINAL PACKAGE) WILL BE ADDED TO THE REVISION FEES. |
| |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| (561)805-6712 |
| [email protected] |
| |
| |