Plan Review Notes For Permit 16060811 |
Permit Number |
16060811 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-06-15 15:04:20 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | | | - PLEASE SITE THE NEC 2011 AS THHE APPLICABLE CODE IN | | THE ELECTRICAL NOTES. | | | | - CHILLER PUMPS SCHEDULE ON SHEET M4.1 SHOWS THE MOTOR | | VOLTAGE AS 460 V 3 PHASE AND THE CHILLER PANEL REFLECTS | | 120/208 V 3 PHASE ? CORRECT AND MATCH. | | | | - ELECTRICAL SUB PERMIT REQUIRED | | | | - PROVIDE ARC-FLASH HAZRD WARNING LABEL IN ACCORDANCE | | WITH NEC 110.16 |
|