2016-06-15 15:04:20REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 - PLEASE SITE THE NEC 2011 AS THHE APPLICABLE CODE IN
 THE ELECTRICAL NOTES.
  
 - CHILLER PUMPS SCHEDULE ON SHEET M4.1 SHOWS THE MOTOR
 VOLTAGE AS 460 V 3 PHASE AND THE CHILLER PANEL REFLECTS
 120/208 V 3 PHASE ? CORRECT AND MATCH.
  
 - ELECTRICAL SUB PERMIT REQUIRED
  
 - PROVIDE ARC-FLASH HAZRD WARNING LABEL IN ACCORDANCE
 WITH NEC 110.16