Plan Review Notes
Plan Review Notes For Permit 16060711
Permit Number 16060711
Review Stop B
Sequence Number 1
Notes
Date Text
2016-06-16 09:04:30PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF SIGNED AND SEALED ENGINEERING
 WITH STRUCTURAL CONNECTION DETAILS. SHOW THE LOCATIONS
 OF THE ANCHORS FOR EACH LETTER AND THE REQUIRED EMBED
 DEPTH AND SPECIFIC ADHESIVE FOR THE STUD ANCHORS ON THE
 DRAWINGS. FBC 107.2.1
  
 2) FBC 107.3.5.1.1(8) - PROVIDE WIND DESIGN
 LOADS/DESIGN PRESSURES PURSUANT TO FBC-CHAPTER 16.
  
 3) SPECIFY THE SUBSTRATE TO WHICH THE SIGN WILL BE
 ATTACHED, ON THE DRAWINGS. FBC 107.2.1