Plan Review Notes For Permit 16060695 |
Permit Number |
16060695 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-06-14 11:24:46 | PLAN REVIEW COMMENTS | | FOR REVISION | | | | 1ST REVIEW: FBC FIFTH EDITION (2014), 2011 NEC | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY ELECTRICAL | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) CHANGES TO THE APPROVED PLANS ARE REQUIRED TO BE | | MADE BY THE DESIGNER OF RECORD, WHICH IN THIS CASE IS | | CHARLES JACKSON. FBC 107.2.1 | | | | 2) THE CHANGES ARE REQUIRED TO BE MADE IN PERMANENT INK | | AND INITIALED AND DATED BY THE DESIGNER OF RECORD. | | PENCIL IS NOT ACCEPTABLE. FBC 107.2.1.4 | | | | 3) THE CHANGES SHOULD BE CLOUDED AND IDENTIFIED BY A | | NUMBER INSIDE A TRIANGLE TO INDICATE THE REVISION | | NUMBER. FBC 107.2.1 | | | | 4) THE TWO REQUIRED PLANS THAT SHOW THE REVISIONS ARE | | REQUIRED TO BE IDENTICAL. THE INFORMATION ON BOTH | | SHEETS ARE REQUIRED TO MATCH. FBC 107.2.1 | | |
|