Plan Review Notes For Permit 16060664 |
Permit Number |
16060664 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-06-25 14:34:56 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 | | [email protected] | | | | FBC FLORIDA BUILDING CODE 5TH EDITION 2014 | | | | TWO COMPLETE COLLATED SETS OF ALL DOCUMENTS REQUIRED | | | | PLEASE NOTE THAT TEST REPORTS ARE REQUIRED - | | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO | | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST | | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE | | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) | | | | | | 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR | | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. | | IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST, | | PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED | | THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE | | GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL | | NOT BE ALTERED. | | | | PLEASE PROVIDE A COPY OF A TEST REPORT WITHOUT THE | | DROPPED CEILING. | | | | |
|