Plan Review Notes For Permit 16060655 |
Permit Number |
16060655 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-06-13 19:04:54 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | | | - PROVIDE FEEDER CONDUIT SIZE ? FBC-107. GROUNDING | | DETAIL TO INCLUDE ELECTRODE WIRE SIZE AND INTERSYSTEM | | BONDING TERMINAL ? NEC 250.50, 250.94 | | | | - CLARIFY WHICH ATS EQUIPMENT IS BEING USED CUT SHEETS | | SHOW 2 MODELS ONE IS NEMA 1 INDOOR AND THE OTHER NEMA 3 | | SERVICE ENTRANCE RATED ? NEC 230.66 SERVICE EQUIPMENT | | RATED AT 600 VOLTS OR | | LESS SHALL BE MARKED TO IDENTIFY IT AS BEING SUITABLE | | FOR USE AS SERVICE EQUIPMENT. |
|