2016-06-13 19:04:54REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 - PROVIDE FEEDER CONDUIT SIZE ? FBC-107. GROUNDING
 DETAIL TO INCLUDE ELECTRODE WIRE SIZE AND INTERSYSTEM
 BONDING TERMINAL ? NEC 250.50, 250.94
  
 - CLARIFY WHICH ATS EQUIPMENT IS BEING USED CUT SHEETS
 SHOW 2 MODELS ONE IS NEMA 1 INDOOR AND THE OTHER NEMA 3
 SERVICE ENTRANCE RATED ? NEC 230.66 SERVICE EQUIPMENT
 RATED AT 600 VOLTS OR
 LESS SHALL BE MARKED TO IDENTIFY IT AS BEING SUITABLE
 FOR USE AS SERVICE EQUIPMENT.