Plan Review Notes For Permit 16060624 |
Permit Number |
16060624 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2017-03-07 14:00:42 | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | ELECTRICAL REVIEW COMMENTS. | | | | INDICATE THE LOCATION OF THE ELECTRICAL PANELS AND | | SUBPANELS. VERIFY THE REQUIRED WORKING CLEARANCES ARE | | MAINTAINED AT ALL ELECTRICAL PANELS. NEC 110.26, FBC R | | E3405.1 | | | | INDICATE THE LOCATION OF THE MAIN DISCONNECT. A MAIN | | ELECTRICAL DISCONNECT IS REQUIRED FOR THE SERVICE AT | | THE POINT WHERE THE BUILDING RECEIVES THE ELECTRICAL | | SUPPLY. UNPROTECTED SERVICE CONDUCTORS SHALL NOT ENTER | | THE BUILDING. FBC E3405, E3603 | | | | AN INTERSYSTEM BONDING SYSTEM IS REQUIRED AT THE | | SERVICE GROUNDING SYSTEM. NEC 250.94; FBC E3609 | | | | THE EXISTING 2ND FLOOR BEDROOM ALSO REQUIRES A SMOKE | | DETECTOR BOTH INSIDE AND OUTSIDE THE ROOM WITH A CARBON | | MONOXIDE DETECTOR WITHIN TEN FEET AS WELL. FBC R314, | | 315 | | | | ALL NEW CIRCUITS MUST BE PROTECTED WITH ARC FAULT | | BREAKERS. FBC E3902.12, NEC 210.12 | | | | | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | 561-805-6654(OFFICE) | | 561-373-3701(CELL) | | | | |
|