2017-03-07 14:00:42PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 INDICATE THE LOCATION OF THE ELECTRICAL PANELS AND
 SUBPANELS. VERIFY THE REQUIRED WORKING CLEARANCES ARE
 MAINTAINED AT ALL ELECTRICAL PANELS. NEC 110.26, FBC R
 E3405.1
  
 INDICATE THE LOCATION OF THE MAIN DISCONNECT. A MAIN
 ELECTRICAL DISCONNECT IS REQUIRED FOR THE SERVICE AT
 THE POINT WHERE THE BUILDING RECEIVES THE ELECTRICAL
 SUPPLY. UNPROTECTED SERVICE CONDUCTORS SHALL NOT ENTER
 THE BUILDING. FBC E3405, E3603
  
 AN INTERSYSTEM BONDING SYSTEM IS REQUIRED AT THE
 SERVICE GROUNDING SYSTEM. NEC 250.94; FBC E3609
  
 THE EXISTING 2ND FLOOR BEDROOM ALSO REQUIRES A SMOKE
 DETECTOR BOTH INSIDE AND OUTSIDE THE ROOM WITH A CARBON
 MONOXIDE DETECTOR WITHIN TEN FEET AS WELL. FBC R314,
 315
  
 ALL NEW CIRCUITS MUST BE PROTECTED WITH ARC FAULT
 BREAKERS. FBC E3902.12, NEC 210.12
  
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER