Plan Review Notes
Plan Review Notes For Permit 16060624
Permit Number 16060624
Review Stop E
Sequence Number 1
Notes
Date Text
2016-06-30 16:10:071ST ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 1. ACCORDING TO THE CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC, CONSTRUCTION DOCUMENTS SUBMITTED FOR
 PERMITTING SHALL INCLUDE THE SPECIFIC CODE TO WHICH THE
 SYSTEM IS DESIGNED. SIMPLY STATING THE LATEST OR
 APPLICABLE IS PERMITTED.
 2. ELECTRICAL NOTE 5 INDICATES SMOKE DETECTOR PLACEMENT
 OUTSIDE THE SLEEPING AREA. SUCH NOTE FAILS TO COMPLY
 WITH FBC-R 314.3. PER FBC 314.3 YOU SHALL HAVE A SMOKE
 DETECTOR ?INSIDE? THE SLEEPING AREA AND ALSO IN THE
 IMMEDIATE AREA OUTSIDE. PLEASE CORRECT THE NOTE AND
 DEVICE PLACEMENT ACCORDINGLY.
 3. PER FBC 314.3.1 YOU SHALL INSTALL SMOKE DETECTORS
 THROUGHOUT THE RESIDENCE AS REQUIRED FOR NEW
 CONSTRUCTION. IF ALREADY DONE SO, DISREGARD THIS
 COMMENT.
 4. PER FBC 315 IF THE RESIDENCE HAS AN ATTACHED GARAGE
 OR ANY FOSSIL FUEL BURNING APPLIANCE YOU SHALL INSTALL
 CARBON MONOXIDE DETECTORS AS INDICATED BY THIS SECTION.
 5. THE WORD ?ROMEX? AS USED IN ELECTRICAL NOTE 13 IS
 INTENDED TO IDENTIFY A TYPE OF CABLE. ROMEX IS A BRAND
 NAME AND NOT A TYPE OF CABLE, REFER TO CABLE TYPES
 ?NM?, ?NMC? OR ?NMS?.
 6. THE SAME APPLIES TO THE REFERENCE TO ?BX? IN
 ELECTRICAL NOTE 14. USE ?MC? CABLE INSTEAD.
 7. FBC-RE4002.14/NEC 406.12 TAMPER-RESISTANT
 RECEPTACLES IN DWELLING UNITS. ALL NEWLY INSTALLED
 125-VOLT, 15 AND 20 AMPERE RECEPTACLES SHALL BE LISTED
 TAMPER RESISTANT.
 8. FBC-RE4001.15/NEC 404.2(C) WHERE SWITCHES
 CONTROLLING LIGHTING LOADS SUPPLIED BY A GROUNDED
 BRANCH CIRCUIT, THE GROUNDED BRANCH CIRCUIT CONDUCTOR
 FOR THE CONTROLLED LIGHTING CIRCUIT SHALL BE PROVIDED
 AT THE SWITCH.
 9. PER NEC 215.5 A SITE SPECIFIC RISER DIAGRAM AND LOAD
 CALCS ARE REQUIRED.
 10. FBC-RE3706.2/NEC 408.4 A PANEL CIRCUIT DIRECTORY IS
 REQUIRED FOR ALL PANELS.
 11. FBC-RE3901.7/NEC 210.52(E)(3) BALCONIES, DECKS, AND
 PORCHES THAT ARE ACCESSIBLE FROM INSIDE THE DWELLING
 UNIT SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET
 INSTALLED WITHIN THE PERIMETER OF THE BALCONY, DECK, OR
 PORCH. THE RECEPTACLE SHALL NOT BE LOCATED MORE THAN
 2.0 M (61?2 FT.) ABOVE THE BALCONY, DECK, OR PORCH
 SURFACE.
 12. FBC-RE3903.4/NEC 210.70(A)(3) STORAGE OR EQUIPMENT
 SPACES. AT LEAST ONE LIGHTING OUTLET CONTAINING A
 SWITCH OR CONTROLLED BY A WALL SWITCH SHALL BE
 INSTALLED WHERE THESE SPACES ARE USED FOR STORAGE OR
 CONTAIN EQUIPMENT REQUIRING SERVICING. THE LIGHTING
 OUTLET SHALL BE PROVIDED AT OR NEAR THE EQUIPMENT
 REQUIRING SERVICING.
 13. IN ADDITION TO THE ABOVE, PROVIDE EITHER ON A SITE
 PLAN OR MARK THE FLOOR PLAN WITH THE LOCATION OF THE
 ELECTRIC METER AND PANELS TO ASCERTAIN COMPLIANCE WITH
 FBC-RE3601.6.2/NEC 230.70(A)(1). THE SERVICE DISCONNECT
 SHALL BE LOCATED IN A READILY ACCESSIBLE LOCATION
 OUTSIDE OF THE BLDG. OR INSIDE AT THE NEAREST POINT OF
 ENTRY OF THE SERVICE CONDUCTORS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,