2016-06-28 15:50:40 | 1ST ELECTRICAL REVIEW NOTES |
| REVIEWED FOR COMPLIANCE WITH: |
| 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| |
| 1. THE APPLICABLE CODE IS THE 5TH EDITION OF THE 2014 |
| FBC-R. CORRECT NOTE ACCORDINGLY. |
| 2. FBC-RE4101.5/NEC 422.31(B) YOU SHALL PROVIDE A |
| DISCONNECT FOR THE WATER HEATER OR MAKE A NOTE AS TO |
| THE MODE OF COMPLIANCE. |
| 3. FBC-RE3901.7/NEC 210.52(E)(3) REQUIRES THAT THERE BE |
| AN OUTLET WITHIN THE PERIMETER OF THE BALCONY. |
| 4. FBC-RE3903.4/NEC 210.70(3) REQUIRES THAT THERE BE AT |
| LEAST ONE SWITCH FOR THE ATTIC LIGHT AT THE POINT OF |
| ENTRY, (IN THE INTEREST OF ENERGY CONSERVATION MAY I |
| SUGGEST THE SWITCH HAVE A PILOT LIGHT AND BE OUTSIDE |
| THE ATTIC ON A WALL VISIBLE TO THE OCCUPANTS). THIS |
| DOES AWAY WITH THE PULL CHAIN AS THE SINGLE SWITCH. |
| FURTHERMORE, THE ACTUAL LUMINAIRE SHALL CLOSE TO THE |
| EQUIPMENT. |
| 5. FBC-RE4003.2/NEC 410.11 REQUIRES THAT LUMINAIRES |
| NEAR COMBUSTIBLE MATERIALS HAVE A GUARD AROUND THE LAMP |
| TO PREVENT CONTACT GREATER THAN 90 DEGREES. THIS |
| ELIMINATES THE EXPOSED LAMP PULL CHAIN FIXTURE IN THE |
| ATTIC. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |