Plan Review Notes
Plan Review Notes For Permit 16060591
Permit Number 16060591
Review Stop M
Sequence Number 1
Notes
Date Text
2016-06-15 16:44:061ST REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING
 PERMIT #16060591
 6/15/16
  
 1) SHEET M-1.01: PLEASE CLARIFY IF THE SEPARATION WALL
 IN DETAIL A IS FIRE-RATED- FIRE DAMPERS ARE REQUIRED
 FOR THE RETURN AIR PLENUM GRILL AND SUPPLY DUCT IF THE
 WALL IS RATED.
  
 2) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER