2016-06-15 16:44:06 | 1ST REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING | | PERMIT #16060591 | | 6/15/16 | | | | 1) SHEET M-1.01: PLEASE CLARIFY IF THE SEPARATION WALL | | IN DETAIL A IS FIRE-RATED- FIRE DAMPERS ARE REQUIRED | | FOR THE RETURN AIR PLENUM GRILL AND SUPPLY DUCT IF THE | | WALL IS RATED. | | | | 2) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE | | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|