Plan Review Notes
Plan Review Notes For Permit 16060591
Permit Number 16060591
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-06-21 11:28:07THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET A 1.01 - NO DOOR SCHEDULE IS INDICATED. THREE
 (3) DOORS ARE NOT SPECIFICALLY INDICATED; THE WAREHOUSE
 STORAGE / CORRIFOR DOOR, THE OPEN OFFICE / CORRIDOR
 DOOR AND THE COMMON LOBBY / CORRIDOR DOOR.
  
 PLEASE PROVIDE APPLICABLE DOOR SCHEDULE INFORMATION,
 INCLUDING HARDWARE, AND DIMENSIONS.
  
  
 2) SHEET A.1.01 - THERE IS AN INDICATION OF AN EMEGENCY
 LIGHT IN OFFICE # 3. IT IS RECOMMENDED TO MOVE THAT
 EMEGENCY LIGHT INTO THE EXIT CORRIDOR.
  
  
 3) SHEET A 1.00 - THERE IS AN INDICATION THAT THE
 BUILDING IS FULLY SPRINKLERED.
  
 PLEASE PROVIDE A NOTE THAT ANY AND ALL WORK ON THE FIRE
 SPRINKLER SYSTEM SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 4) SHEET E 1.01 - THERE ARE NO INDICATIONS OF ANY FIRE
 ALARM DEVICES.
  
 PLEASE VERIFY AND PROVIDE A NOTE SAYING NO FIRE A,ARM
 DEVICES; HOWEVER, IF THEY ARE EXISTING PROVIDE
 LOCATIONS.
  
 ADDITIONALLY, PLEASE PROVIDE A NOTE THAT ANY AND ALL
 WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE UNDER
 SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE SAFETY
 CONTRACTORS.
  
 5) SHEET M 1.01 - THERE IS NO INDICATION OF THE SIXE OF
 THE A/C SYSTEM.
  
 DUCT DETECTORS
 PER NFPA 90 A , CHAPTER 6 CONTROLS
 6.4* SMOKE DETECTION FOR AUTOMATIC CONTROL.
 6.4.1 TESTING. ALL AUTOMATIC SHUTDOWN DEVICES SHALL BE
 TESTED AT LEAST ANNUALLY.
 6.4.2* LOCATION.
 6.4.2.1 SMOKE DETECTORS LISTED FOR USE IN AIR
 DISTRIBUTION SYSTEMS SHALL BE LOCATED AS FOLLOWS:
 (1) DOWNSTREAM OF THE AIR FILTERS AND AHEAD OF ANY
 BRANCH CONNECTIONS IN AIR SUPPLY SYSTEMS HAVING A
 CAPACITY GREATER THAN 944 L/SEC (2000 FT3/MIN)
 (2) AT EACH STORY PRIOR TO THE CONNECTION TO A COMMON
 RETURN AND PRIOR TO ANY RECIRCULATION OR FRESH AIR
 INLET CONNECTION IN AIR RETURN SYSTEMS HAVING A
 CAPACITY GREATER THAN 7080 L/SEC (15,000 FT3/MIN) AND
 SERVING MORE THAN ONE STORY
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  