2016-06-21 11:28:07 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) SHEET A 1.01 - NO DOOR SCHEDULE IS INDICATED. THREE |
| (3) DOORS ARE NOT SPECIFICALLY INDICATED; THE WAREHOUSE |
| STORAGE / CORRIFOR DOOR, THE OPEN OFFICE / CORRIDOR |
| DOOR AND THE COMMON LOBBY / CORRIDOR DOOR. |
| |
| PLEASE PROVIDE APPLICABLE DOOR SCHEDULE INFORMATION, |
| INCLUDING HARDWARE, AND DIMENSIONS. |
| |
| |
| 2) SHEET A.1.01 - THERE IS AN INDICATION OF AN EMEGENCY |
| LIGHT IN OFFICE # 3. IT IS RECOMMENDED TO MOVE THAT |
| EMEGENCY LIGHT INTO THE EXIT CORRIDOR. |
| |
| |
| 3) SHEET A 1.00 - THERE IS AN INDICATION THAT THE |
| BUILDING IS FULLY SPRINKLERED. |
| |
| PLEASE PROVIDE A NOTE THAT ANY AND ALL WORK ON THE FIRE |
| SPRINKLER SYSTEM SHALL BE DONE UNDER SEPARATE SHOP |
| DRAWINGS BY CERTIFIED LIFE SAFETY CONTRACTORS. |
| |
| 4) SHEET E 1.01 - THERE ARE NO INDICATIONS OF ANY FIRE |
| ALARM DEVICES. |
| |
| PLEASE VERIFY AND PROVIDE A NOTE SAYING NO FIRE A,ARM |
| DEVICES; HOWEVER, IF THEY ARE EXISTING PROVIDE |
| LOCATIONS. |
| |
| ADDITIONALLY, PLEASE PROVIDE A NOTE THAT ANY AND ALL |
| WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE UNDER |
| SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE SAFETY |
| CONTRACTORS. |
| |
| 5) SHEET M 1.01 - THERE IS NO INDICATION OF THE SIXE OF |
| THE A/C SYSTEM. |
| |
| DUCT DETECTORS |
| PER NFPA 90 A , CHAPTER 6 CONTROLS |
| 6.4* SMOKE DETECTION FOR AUTOMATIC CONTROL. |
| 6.4.1 TESTING. ALL AUTOMATIC SHUTDOWN DEVICES SHALL BE |
| TESTED AT LEAST ANNUALLY. |
| 6.4.2* LOCATION. |
| 6.4.2.1 SMOKE DETECTORS LISTED FOR USE IN AIR |
| DISTRIBUTION SYSTEMS SHALL BE LOCATED AS FOLLOWS: |
| (1) DOWNSTREAM OF THE AIR FILTERS AND AHEAD OF ANY |
| BRANCH CONNECTIONS IN AIR SUPPLY SYSTEMS HAVING A |
| CAPACITY GREATER THAN 944 L/SEC (2000 FT3/MIN) |
| (2) AT EACH STORY PRIOR TO THE CONNECTION TO A COMMON |
| RETURN AND PRIOR TO ANY RECIRCULATION OR FRESH AIR |
| INLET CONNECTION IN AIR RETURN SYSTEMS HAVING A |
| CAPACITY GREATER THAN 7080 L/SEC (15,000 FT3/MIN) AND |
| SERVING MORE THAN ONE STORY |
| |
| |
| 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |