Plan Review Notes For Permit 16060583
Permit Number 16060583
Review Stop E
Sequence Number 1
Notes
Date Text
2016-06-20 18:21:27REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 - FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE
 SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE
 LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUIT
 OCPD.
  
 - NEC 300.5(D)(1)(2)(3)(4) PROTECTION FROM PHYSICAL
 DAMAGE OF SERVICE CONDUCTORS, WARNING RIBBON PLACED 12'
 ABOVE UNDERGROUND SERVICE CONDUCTORS.
  
 - IF EQUIPMENT IS SUBJECT TO VEHICULAR TRAFFIC PROPER
 GUARDING MIGHT BE REQUIRED. NEC 110.26 (E)(2) , NEC
 110.27
  
 - PROVIDE A MOUNTING DETAIL OF ELECTRICAL EQUIPMENT
 SHOWING HOW IT WILL BE INSTALLED MECHANICALLY.
  
  