2016-06-16 13:32:41 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) THE ADDRESS ON THE APPLICATION, 501 EVERNIA ST, DOES |
| NOT MATCH THE ADDRESS ON THE TITLE BLOCK, 520 DATURA |
| ST, |
| |
| PLEASE CLARIFY/CORRECT. |
| |
| 2) DESIGN AREA 2 INDICATES AN AREA OF SPRINKLER |
| OPERATION DENSITY OF 900. THE ENGINEER OF RECORD PER |
| THE MASTER PERMIT # 15110807 INDICATES 1500 SQ FT. |
| |
| THE SUBMITTAL DOES NOT APPEAR TO HAVE AN APPROVAL FROM |
| THE ENGINEER OF RECORD PER MASTER PERMIT # 15110807 FOR |
| THIS CHANGE. |
| |
| 3) THE SUBMITTED PLANS ARE NOT BOUND/ORGANIZED. |
| |
| PLEASE BIND ALL SHEETS SO THEY CAN NOT BECOME LOST, |
| REMOVED OR DISORGANIZED. |
| |
| 4) FIRE SPRINKLER SPECIFICATION SHEETS ARE NOT INCLUDED |
| WITH THE SUMITTAL. |
| |
| PLEASE PROVIDE SPEC SHEETS FOR THE TYPE OF EQUIPMENT |
| BEING INSTALLED. |
| |
| 5) THE DESIGN AREAS ARE NOT CLEARLY INDICATED ON THE |
| INDICATING SHEETS. THERE APPEARS TO BE DASHED LINES BUT |
| ALSO CLOUDED AREAS ON THE SAME SHEET. |
| |
| PLEASE PROVIDE DEFINITIVE LINES FOR EACH DESIGN AREA |
| AND REMOVE ANY UNNECESSARY INDICATORS. |
| |
| 6) NO DIMENSIONS ARE PROVIDED FOR THE DESIGN AREAS. |
| |
| PLEASE PROVIDE DIMENSIONS OF EACH DESIGN AREA FOR |
| VERIFICATION PRUPOSES. |
| |
| 7) THE AREAS OF THE OPEN STAIRWAYS DO NOT INDICATE FIRE |
| SPRINKLER PROTECTION PER NFPA 8.15.4 |
| |
| 8.15.4.1* GENERAL. UNLESS THE REQUIREMENTS OF 8.15.4.4 |
| ARE |
| MET, WHERE MOVING STAIRWAYS, STAIRCASES, OR SIMILAR |
| FLOOR OPENINGS |
| ARE UNENCLOSED AND WHERE SPRINKLER PROTECTION IS |
| SERVING |
| AS THE ALTERNATIVE TO ENCLOSURE OF THE VERTICAL |
| OPENING, THE |
| FLOOR OPENINGS INVOLVED SHALL BE PROTECTED BY CLOSELY |
| SPACED |
| SPRINKLERS IN COMBINATION WITH DRAFT STOPS IN |
| ACCORDANCE WITH |
| 8.15.4.2 AND 8.15.4.3. |
| |
| PLEASE PROVIDE FOR COMPLAINCE OR PROVIDE A DETAILED |
| NARRATIVE OF EXPLANATION OF WHY IT MAY NOT BE REQUIRED. |
| |
| 8) ONLY ONE SET OF HYDRALIC CALCULATION ARE PROVIDED. |
| |
| PLEASE PROVIDE ANOTHER SET OF HYDRALIC CALCULATIONS, |
| ONE PER EACH PLAN SET. |
| |
| 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |