2016-06-16 13:32:41THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE ADDRESS ON THE APPLICATION, 501 EVERNIA ST, DOES
 NOT MATCH THE ADDRESS ON THE TITLE BLOCK, 520 DATURA
 ST,
  
 PLEASE CLARIFY/CORRECT.
  
 2) DESIGN AREA 2 INDICATES AN AREA OF SPRINKLER
 OPERATION DENSITY OF 900. THE ENGINEER OF RECORD PER
 THE MASTER PERMIT # 15110807 INDICATES 1500 SQ FT.
  
 THE SUBMITTAL DOES NOT APPEAR TO HAVE AN APPROVAL FROM
 THE ENGINEER OF RECORD PER MASTER PERMIT # 15110807 FOR
 THIS CHANGE.
  
 3) THE SUBMITTED PLANS ARE NOT BOUND/ORGANIZED.
  
 PLEASE BIND ALL SHEETS SO THEY CAN NOT BECOME LOST,
 REMOVED OR DISORGANIZED.
  
 4) FIRE SPRINKLER SPECIFICATION SHEETS ARE NOT INCLUDED
 WITH THE SUMITTAL.
  
 PLEASE PROVIDE SPEC SHEETS FOR THE TYPE OF EQUIPMENT
 BEING INSTALLED.
  
 5) THE DESIGN AREAS ARE NOT CLEARLY INDICATED ON THE
 INDICATING SHEETS. THERE APPEARS TO BE DASHED LINES BUT
 ALSO CLOUDED AREAS ON THE SAME SHEET.
  
 PLEASE PROVIDE DEFINITIVE LINES FOR EACH DESIGN AREA
 AND REMOVE ANY UNNECESSARY INDICATORS.
  
 6) NO DIMENSIONS ARE PROVIDED FOR THE DESIGN AREAS.
  
 PLEASE PROVIDE DIMENSIONS OF EACH DESIGN AREA FOR
 VERIFICATION PRUPOSES.
  
 7) THE AREAS OF THE OPEN STAIRWAYS DO NOT INDICATE FIRE
 SPRINKLER PROTECTION PER NFPA 8.15.4
  
 8.15.4.1* GENERAL. UNLESS THE REQUIREMENTS OF 8.15.4.4
 ARE
 MET, WHERE MOVING STAIRWAYS, STAIRCASES, OR SIMILAR
 FLOOR OPENINGS
 ARE UNENCLOSED AND WHERE SPRINKLER PROTECTION IS
 SERVING
 AS THE ALTERNATIVE TO ENCLOSURE OF THE VERTICAL
 OPENING, THE
 FLOOR OPENINGS INVOLVED SHALL BE PROTECTED BY CLOSELY
 SPACED
 SPRINKLERS IN COMBINATION WITH DRAFT STOPS IN
 ACCORDANCE WITH
 8.15.4.2 AND 8.15.4.3.
  
 PLEASE PROVIDE FOR COMPLAINCE OR PROVIDE A DETAILED
 NARRATIVE OF EXPLANATION OF WHY IT MAY NOT BE REQUIRED.
  
 8) ONLY ONE SET OF HYDRALIC CALCULATION ARE PROVIDED.
  
 PLEASE PROVIDE ANOTHER SET OF HYDRALIC CALCULATIONS,
 ONE PER EACH PLAN SET.
  
 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709