2016-06-29 09:34:14720 8TH STREET
 PERMIT #16060377
 MASTER #10010548
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT: INSTALLATION SHALL COMPLY WITH THE 2010
 EDITION OF NFPA 13 NOT THE 2007 EDITION.
  
 RESPONSE COMMENT: PER NFPA 13 SECTION 11.2.3.3.3, TO
 UTILIZE THE ROOM DESIGN METHOD, ALL ROOMS SHALL BE
 ENCLOSED WITH WALLS HAVING A FIRE-RESISTANCE RATING
 EQUAL TO THE WATER SUPPLY DURATION INDICATED IN TABLE
 11.2.3.1.2.
 ORIGINAL COMMENT: THE HYDRAULIC CALCULATION HAS THE
 LONG SIDE (1.2 X THE SQUARE ROOT OF THE AREA OF
 SPRINKLER OPERATION) OF THE HYDRAULIC AREA DRAWN
 PERPENDICULAR TO THE BRANCH LINES WHEN THE LONG SIDE OF
 THE HYDRAULIC AREA SHOULD BE RUN PARALLEL TO THE BRANCH
 LINES PER NFPA 13 (2010 EDITION) SECTION
 22.4.4.1.1.1.PROVIDE A HYDRAULIC CALCULATION FOR THE
 SOUTHEAST AREA OF THE SECOND FLOOR (EDUCATIONAL ROOMS)
 WHERE THE PIPING CONFIGURATION SHOWS 8 SPRINKLERS
 SUPPLIED FROM A 2-INCH BRANCHLINE.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE