 REVIEW COMMENTS - FIRE DEPARTMENT
  
 INSTALLATION SHALL COMPLY WITH THE 2010 EDITION OF NFPA
 13 NOT THE 2007 EDITION.
  
 PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT
 CONNECTION.
  
 THE EXTENDED COVERAGE SPRINKLER LOCATED IN THE SECOND
 FLOOR CEILING IS PROTECTING THE FIRST FLOOR'S FLOR AREA
 AND SHOULD BE PIPED SO A WATER FLOW ALARM IS ACHIEVED
 ON THE FIRST FLOOR AND NOT THE SECOND FLOOR SO ARRIVING
 FIREFIGHTERS DO NOT ASSUME THE FIRE IS ON THE SECOND
 FLOOR.
  
 NO HYDRAULIC CALCULATIONS SUBMITTED SUPPORTING THE
 WATER CURTAIN DEMAND FOR THE FIRST FLOOR OPENING. UPPER
 CEILING HEIGHT MAY EXCEED THE 20 FOOT THRESHOLD FOR THE
 AREA REDUCTION METHOD FOR QUICK RESPONSE SPRINKLERS.
 PER NFPA 13 SECTION 11.3.3.3 IF A SINGLE FIRE CAN BE
 EXPECTED TO OPERATE SPRINKLERS WITHIN THE WATER CURTAIN
 AND WITHIN THE DESIGN AREA OF A HYDRAULICALLY
 CALCULATED SYSTEM, THE WATER SUPPLY TO THE WATER
 CURTAIN SHALL BE ADDED TO THE WATER DEMAND OF THE
 HYDRAULIC CALCULATIONS AND SHALL BE BALANCED TO THE
 CALCULATED AREA DEMAND. HYDRAULIC DESIGN CALCULATIONS
 SHALL INCLUDE A DESIGN AREA SELECTED TO INCLUDE CEILING
 SPRINKLERS ADJACENT TO THE WATER CURTAIN.
  
 THE MAIN CORRIDOR ON THE SECOND FLOOR IS PROTECTED BY
 EXTENDED COVERAGE SPRINKLERS; HOWEVER, THERE ARE LOWER
 SOFFITS IN THIS CORRIDOR THAT DO NOT APPEAR TO BE
 PROPERLY PROTECTED DUE TO SPRAY OBSTRUCTIONS CAUSED BY
 CEILING/SOFFIT HEIGHT DIFFERENCES.
  
 THE HYDRAULIC CALCULATION HAS THE LONG SIDE (1.2 X THE
 SQUARE ROOT OF THE AREA OF SPRINKLER OPERATION) OF THE
 HYDRAULIC AREA DRAWN PERPENDICULAR TO THE BRANCH LINES
 WHEN THE LONG SIDE OF THE HYDRAULIC AREA SHOULD BE RUN
 PARALLEL TO THE BRANCH LINES PER NFPA 13 (2010 EDITION)
 SECTION 22.4.4.1.1.1.
  
 PROVIDE A HYDRAULIC CALCULATION FOR THE SOUTHEAST AREA
 OF THE SECOND FLOOR (EDUCATIONAL ROOMS) WHERE THE
 PIPING CONFIGURATION SHOWS 8 SPRINKLERS SUPPLIED FROM A
 2-INCH BRANCHLINE.
  