2016-07-15 09:24:03APPROVED WITH EXCEPTIONS
 1) FBC ACCESSIBILITY SECTION 505.4 REQUIRES THE TOP OF
 THE RAMP AND LANDING HANDRAILS TO BE A MAXIMUM OF 36
 INCHES MEASURED VERTICALLY ABOVE WALKING SURFACES AND
 RAMPS. FBC 1013.2 REQUIRES GUARDS WHEN THE RAMPS AND
 LANDINGS ARE MORE THAN 30 INCHES MEASURED VERTICALLY
 FROM GRADE AT ANY POINT WITHIN 36" HORIZONTALLY TO THE
 OPEN SIDE. THIS RAMP AND LANDING IS 21" ABOVE GRADE PER
 THE PLANS, SO ONLY THE HANDRAILS ARE REQUIRED.
  
 2) FBC ACCESSIBILITY SECTION 307.4 REQUIRES THE
 HANDRAIL EXTENSION RETURN TO BE 27 INCHES MAXIMUM ABOVE
 THE LOWER LANDING.
  