2016-06-09 11:06:57525 SOUTH FLAGLER DRIVE - 5TH FLOOR
 PERMIT #14090028
 TRACKING #16060212
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET S-2: PROVIDE NONCOMBUSTIBLE FLAME CERTIFICATE FOR
 THE CANOPY MATERIAL.
  
 SHEET S-4: PLAN INDICATES A NEW KITCHEN ISLAND. WHAT
 COOKING APPLIANCES ARE INTENDED TO BE INSTALLED?
  
 SHEET S-7: PLAN INDICATES EXISTING TENT STRUCTURE WITH
 NEW BARBEQUE GRILL. THE COOKING GRILL LOCATED ON THE
 POOL DECK SHALL COMPLY WITH NFPA 96 OR SHALL BE LOCATED
 AT LEAST 10 FEET FROM ANY BUILDING, STRUCTURE, OR
 COMBUSTIBLES PER NFPA 1 SECTION 10.11.6.1. IF THE GRILL
 WILL BE USED UNDER A ROOF STRUCTURE, THE DESIGN SHALL
 COMPLY WITH NFPA 96. LISTED EQUIPMENT PERMANENTLY
 INSTALLED IN ACCORDANCE WITH ITS LISTING, APPLICABLE
 CODES, AND MANUFACTURER?S INSTRUCTIONS SHALL BE
 PERMITTED.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  
  
  
  