Plan Review Notes
Plan Review Notes For Permit 16060212
Permit Number 16060212
Review Stop B
Sequence Number 1
Notes
Date Text
2016-06-09 07:39:33BUILDING PLAN REVIEW
 REVISION: 16060212
 PERMIT: 14090028
 ADD: 525 S FLAGLER DR, COMMON FLOOR AREA
 CONT: URBAN DESIGN CONCEPTS
 TEL: (561)301-9506
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JUNE 09/2016
 ACTION: DENIED
  
 1) THE WIND DESIGN UNDER THE 2010 FBC-B HAS NOT BEEN
 PROVIDEDPLEASE NOTE THE EXPOSURE IS A EXPOSURE D.
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 1.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
 1.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
 1.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
 1.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
 1.5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2) .
  
 2) THE S-SHEETS DOES NOT INCLUDE THE DESIGN CRITERIA
 UNDER SECTION 3105 OF THE FBC-B FOR RIGID FRAME
 STRUCTURES.
  
 3) THE PLANS DO NOT INCLUDE CODE LANGUAGE FOR
 COMPLIANCE WITH: 2010 FBC-B 3105.3.1. FABRIC USED FOR
 AWNINGS OR FABRIC-COVERED FRAMES SHALL MEET THE FLAME
 PROPAGATION PERFORMANCE CRITERIA OF NFPA 701.
  
 4) SHEET S-3 INDICATES A NEW 6 FT. TALL FRAMELESS GLASS
 GUARD RAIL. THE PLANS HAVE CROSS SECTION DETAILS THAT
 ARE NOT CLEAR AS TO HOW COMPLIANCE WITH SECTIONS LISTED
 BELOW ARE GOING TO BE MET:
  
 2010FBC-B:
 1607.7.1 HANDRAILS AND GUARDS. HANDRAILS AND GUARDS
 SHALL BE DESIGNED TO RESIST A LOAD OF 50 POUNDS PER
 LINEAR FOOT (PLF) (0.73 KN/M) APPLIED IN ANY DIRECTION
 AT THE TOP AND TO TRANSFER THIS LOAD THROUGH THE
 SUPPORTS TO THE STRUCTURE. GLASS HANDRAIL ASSEMBLIES
 AND GUARDS SHALL ALSO COMPLY WITH SECTION 2407.
  
 1607.1.1CONCENTRATED LOADS. HANDRAILS AND GUARDS SHALL
 BE ABLE TO RESIST A SINGLE CONCENTRATED LOAD OF 200
 POUNDS (0.89 KN), APPLIED IN ANY DIRECTION AT ANY POINT
 ALONG THE TOP, AND TO TRANSFER THIS LOAD THROUGH THE
 SUPPORTS TO THE STRUCTURE. THIS LOAD NEED NOT BE
 ASSUMED TO ACT CONCURRENTLY WITH THE LOADS SPECIFIED IN
 SECTION 1607.7.1.
 1607.7.1.2 COMPONENTS.
  
 1607.7.1.2 COMPONENTS. INTERMEDIATE RAILS (ALL THOSE
 EXCEPT THE HANDRAIL), BALUSTERS AND PANEL FILLERS SHALL
 BE DESIGNED TO WITHSTAND A HORIZONTALLY APPLIED NORMAL
 LOAD OF 50 POUNDS (0.22 KN) ON AN AREA EQUAL TO 1
 SQUARE FOOT (0.0929 M2), INCLUDING OPENINGS AND SPACE
 BETWEEN RAILS. REACTIONS DUE TO THIS LOADING ARE NOT
 REQUIRED TO BE SUPERIMPOSED WITH THOSE OF SECTION
 1607.7.1 OR 1607.7.1.1.
  
 2407.1.1 LOADS. THE PANELS AND THEIR SUPPORT SYSTEM
 SHALL BE DESIGNED TO WITHSTAND THE LOADS SPECIFIED IN
 SECTION 1607.7. A SAFETY FACTOR OF FOUR SHALL BE USED.
  
 2407.1.4 GLAZING IN WIND-BORNE DEBRIS REGIONS. GLAZING
 INSTALLED IN IN-FILL PANELS OR BALUSTERS IN WIND-BORNE
 DEBRIS REGIONS SHALL COMPLY WITH THE FOLLOWING:
  
 2407.1.4.1 BALLUSTERS AND IN-FILL PANELS. GLASS
 INSTALLED IN EXTERIOR RAILING IN-FILL PANELS OR
 BALUSTERS SHALL BE LAMINATED GLASS COMPLYING WITH
 CATEGORY II OF CPSC 16 CFR 1201 OR CLASS A OF ANSI
 Z97.1.
  
 2407.1.4.2 GLASS SUPPORTING TOP RAIL. WHEN THE TOP RAIL
 IS SUPPORTED BY GLASS, THE ASSEMBLY SHALL BE TESTED
 ACCORDING TO THE IMPACT REQUIREMENTS OF SECTION
 1609.1.2. THE TOP RAIL SHALL REMAIN IN PLACE AFTER
 IMPACT.
  
 5)