Plan Review Notes
Plan Review Notes For Permit 16060185
Permit Number 16060185
Review Stop M
Sequence Number 1
Notes
Date Text
2016-06-10 14:24:361ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16060185
 6/10/16
  
 1) PROVIDE A LIST OF CURRENT CODES AND STANDARDS USED
 IN THE DESIGN OF THE PROJECT- SECTION 101.2 FBC-14
 BUILDING.
  
 2) PROVIDE THE LEVEL OF ALTERATION PER CHAPTER 5 FBC-14
 EXISTING BUILDING.
  
 3) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A TABLE ON THE PLAN INDICATING THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR FOR THE NEW LOCKER ROOMS.
  
 4) IN ACCORDANCE WITH TABLE 403.3 THE LOCKERS ROOMS
 MUST HAVE EXHAUST VENTILATION RATES OF .25 CFM'S PER
 SQUARE FOOT. PROVIDE EXHAUST CALCULATIONS ON THE PLAN
 FOR BOTH THE LOCKER ROOMS AND THE MEN'S AND WOMEN'S
 BATHROOMS. IT APPEARS THAT NO EXHAUST SYSTEM HAS BEEN
 PROVIDED FOR THE LOCKER ROOMS- PLEASE REVISE THE PLANS
 TO MEET COMPLIANCE, AND SEE FOOTNOTE G CONCERNING THE
 TRANSFER DUCTS: THE TRANSFER CFM'S SHALL NOT EXCEED 10%
 OF THE AIR IN THE LOCKER AND BATHROOM SPACES.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  