Plan Review Notes For Permit 16060185 |
Permit Number |
16060185 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-06-10 14:24:36 | 1ST REVIEW: FBC 2014 MECHANICAL | | PERMIT #16060185 | | 6/10/16 | | | | 1) PROVIDE A LIST OF CURRENT CODES AND STANDARDS USED | | IN THE DESIGN OF THE PROJECT- SECTION 101.2 FBC-14 | | BUILDING. | | | | 2) PROVIDE THE LEVEL OF ALTERATION PER CHAPTER 5 FBC-14 | | EXISTING BUILDING. | | | | 3) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE | | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. | | PROVIDE A TABLE ON THE PLAN INDICATING THE REQUIRED AND | | PROVIDED CFMS OF OUTDOOR AIR FOR THE NEW LOCKER ROOMS. | | | | 4) IN ACCORDANCE WITH TABLE 403.3 THE LOCKERS ROOMS | | MUST HAVE EXHAUST VENTILATION RATES OF .25 CFM'S PER | | SQUARE FOOT. PROVIDE EXHAUST CALCULATIONS ON THE PLAN | | FOR BOTH THE LOCKER ROOMS AND THE MEN'S AND WOMEN'S | | BATHROOMS. IT APPEARS THAT NO EXHAUST SYSTEM HAS BEEN | | PROVIDED FOR THE LOCKER ROOMS- PLEASE REVISE THE PLANS | | TO MEET COMPLIANCE, AND SEE FOOTNOTE G CONCERNING THE | | TRANSFER DUCTS: THE TRANSFER CFM'S SHALL NOT EXCEED 10% | | OF THE AIR IN THE LOCKER AND BATHROOM SPACES. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|