Plan Review Notes For Permit 16060185 |
Permit Number |
16060185 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-06-25 15:01:35 | INITIAL ELECTRICAL PLAN REVIEW | | | | APPLICABLE CODES IN EFFECT: | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70- 2011 NEC | | COMMENTS: | | | | 1. PROVIDE SIZE OF THE OVERCURRENT PROTECTION AT PANEL | | GDA. | | 2. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED | | SEPARATE PERMITS AND DATA CUT SHEET SUBMITTALS FOR FIRE | | ALARM SHOWN AND ASSOCIATED EQUIPMENT. A NOTE WILL | | SUFFICE. | | 3. PROVIDE A ?? DETAIL OF THE MECHANICAL ROOM WHERE | | EQUIPMENT IS BEING RELOCATED. PROVIDE CLEARANCES. NEC | | 110.26 | | 4. ADDRESS MECHANICAL COMMENTS FOR A COMPLETE REVIEW. | | 5. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE | | TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING | | THIS PROJECT. | | | | | | VALENTINO PEREZ | | ELECTRICAL PLANS EXAMINER II | | 561-805-6717 | | [email protected] | | | | | | | | | | |
|