Plan Review Notes For Permit 16060161 |
Permit Number |
16060161 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-06-07 15:17:58 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. ASSEMBLY PROPOSED IS NOT CLEAR. TWO ASSEMBLIES WERE | | INCLUDED WITH THE NOA. ONE HAS A DP LIMIT OF -52.5 BUT | | REFERS TO GENERAL LIMITATION #9 (NO ENHANCED FASTENING) | | AND IS NOT CONSISTENT WITH THE CALCULATIONS PROVIDED BY | | SANDRA PUERTA, AR. | | | | THE OTHER ASSEMBLY HAS A LIMITATION OF -127.5, SO IS | | ALSO NOT CONSISTENT WITH THE CALCULATIONS. | | | | FBC 5TH ED RESIDENTIAL 301, PROVIDE ASSEMBLY PROPOSED | | AND CALCULATIONS CONSISTENT WITH THE ASSEMBLY. | | | | 2. PROVIDE A SITE PLAN AND ROOF PLAN, FBC 107. THE | | APPLICATION INCLUDES TWO ADDRESSES. A SEPARATE PERMIT | | IS REQUIRED FOR EACH STRUCTURE, IF APPLICABLE. | | | | |
|