2016-06-06 05:15:45 | 1) SHOW THE CORRESPONDING EHD NUMBER OF THE CORRUGATED |
| STAINLESS STEEL TUBING FOR EACH PIPE SIZE. WPB |
| AMENDMENTS TO FBC SEC.107.2.1. |
| |
| 2) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (METER |
| OR MP REGULATOR) TO THE MOST REMOTE OUTLET IN THE |
| BUILDING AND / OR SYSTEM PER THE 2014 FBC-FUEL GAS |
| SEC.402.4.1 OR 2014 FBC-RES. SEC. G 2413.3. |
| |
| 3) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES. |
| SEC. G2413.2. . |
| |
| 4) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / |
| INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014 |
| FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED |
| AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. |
| |
| 5) SHOW THE PIPE SIZE OF THE PIPE ON THE OUTLET OF THE |
| METER. |
| |
| 6) SIZE THE LINE TO THE COOKTOP. |
| |
| 7) SHOW THE DISTANCE FROM THE REGULATORS TO THE |
| APPLIANCE AND SIZE THE LINES FROM THE REGULATORS TO THE |
| APPLIANCE. |
| |
| 8) SUBMIT COPIES OF THE GAS SIZING TABLES USED TO |
| DESIGN THE SYSTEM OR WRITE THE NUMBER OF THE SIZING |
| TABLE ON THE PLAN FROM THE 2014 FBC- RES. SEC. G2413. |
| |