Plan Review Notes
Plan Review Notes For Permit 16060022
Permit Number 16060022
Review Stop G
Sequence Number 1
Notes
Date Text
2016-06-02 12:40:191) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED
 ABOVEGROUND & THE PIPE SIZES. WPB AMENDMENTS TO FBC
 SEC.107.2.1.
  
 2) TYPE OF GAS (LP OR NATURAL).
  
 3) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES.
 SEC. G2413.2. .
  
 4) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 5) SUBMIT COPIES OF THE APPLICABLE SIZING TABLES FROM
 THE 2014 FUEL GAS CODE OR PLACE THE NUMBER OF THE
 APPLICABLE SIZING TABLES ON BOTH SETS OF PLANS.WPB
 AMENDMENTS TO FBC SEC.107.2.1.
  
 6) SHOW THE LOCATION OF ALL STEP DOWN REGULATORS ( IF
 APPLICABLE) AND THE LENGTH AND TYPE OF PIPE FROM EACH
 REGULATOR TO THE APPLIANCE.WPB AMENDMENTS TO FBC
 SEC.107.2.1.
  
 7) SUBMIT A PLAN OF THE BUILDING FOOTPRINT SHOWING THE
 LOCATION OF THE METER AND THE TANKLESS WATER HEATER.
 WPB AMENDMENTS TO FBC SEC.107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  