2016-06-02 17:23:34JOB PERMIT NUMBER: 1606008
 JOB ADDRESS: 908 8TH STREET
 WEST PALM BEACH FLORIDA
 DATE: JUNE 2 2016
  ELECTRICAL PLAN REVIEW COMMENTS
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - NEC 210.12(A) ARC- FAULT PROTECTION REQUIRED IN ALL
 AREAS SPECIFIED UNDER THIS SECTION NOT JUST BEDROOMS,
 PLEASE CHANGE NOTE # 29 TO COMPLY WITH THIS CODE
 ARTICLE.
 - NEC 406.11 TAMPER-RESISTANT RECEPTACLES IN DWELLING
 UNITS. IN ALL AREAS SPECIFIED IN 210.52, ALL 125-VOLT,
 15 AND 20 AMPERE RECEPTACLES SHALL BE LISTED TAMPER
 RESISTANT RECEPTACLES.
 - R315.1 CARBON MONOXIDE PROTECTION. EVERY SEPARATE
 BUILDING OR AN ADDITION TO AN EXISTING BUILDING FOR
 WHICH A PERMIT FOR NEW CONSTRUCTION IS ISSUED AND
 HAVING A FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A
 FIREPLACE, AN ATTACHED GARAGE, OR OTHER FEATURE,
 FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE AS
 BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL
 CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET (3048
 MM) OF EACH ROOM USED FOR SLEEPING PURPOSES.(VERIFY IF
 APPLICABLE)
 - MODIFY AND RE-CALCULATE THE LOAD CLACS IT SEEMS YOU
 WENT WITH THE OPTIONAL METHOD, THEREFORE WITH THE 3 VA
 FOR THE GENERAL LIGHTING , THE 2 SMALL APPLIANCE(1500
 EACH) AND LAUNDRY CIRCUIT (1500), PLUS THE SUM OF THE
 NAMEPLATE RATING OF ELECTRICAL EQUIPMENT YOUR
 CALCULATIONS ARE UNDERSIZED THE DEMAND LOAD INCLUDING
 THE A/C HEAT ACCORDING TO YOUR INFORMATION CAME OUT TO
 BE 108 AMPS SO THE 100 AMP SERVICE IS INSUFFICIENT. THE
 RISER DIAGRAM WILL ALSO HAVE TO BE RE-ADJUSTED TO
 COMPLY WITH NEC 220.82(A)(B)(C) FEEDER AND SERVICE
 CALCULATIONS.
 - NEC 250.56 - SERVICE GROUNDING ELECTRODE TO BE
 AUGMENTED BY AN ADDITIONAL ELECTRODE 6FEET AWAY OR
 PROVIDE EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR
 LESS.
 - NEC 250.94 BONDING FOR OTHER SYSTEMS. THE
 INTER-SYSTEM BONDING TERMINAL PRESCRIBED SHALL BE
 INSTALLED.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER