2016-06-02 17:23:34 | JOB PERMIT NUMBER: 1606008 |
| JOB ADDRESS: 908 8TH STREET |
| WEST PALM BEACH FLORIDA |
| DATE: JUNE 2 2016 |
| ELECTRICAL PLAN REVIEW COMMENTS |
| THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| |
| - NEC 210.12(A) ARC- FAULT PROTECTION REQUIRED IN ALL |
| AREAS SPECIFIED UNDER THIS SECTION NOT JUST BEDROOMS, |
| PLEASE CHANGE NOTE # 29 TO COMPLY WITH THIS CODE |
| ARTICLE. |
| - NEC 406.11 TAMPER-RESISTANT RECEPTACLES IN DWELLING |
| UNITS. IN ALL AREAS SPECIFIED IN 210.52, ALL 125-VOLT, |
| 15 AND 20 AMPERE RECEPTACLES SHALL BE LISTED TAMPER |
| RESISTANT RECEPTACLES. |
| - R315.1 CARBON MONOXIDE PROTECTION. EVERY SEPARATE |
| BUILDING OR AN ADDITION TO AN EXISTING BUILDING FOR |
| WHICH A PERMIT FOR NEW CONSTRUCTION IS ISSUED AND |
| HAVING A FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A |
| FIREPLACE, AN ATTACHED GARAGE, OR OTHER FEATURE, |
| FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE AS |
| BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL |
| CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET (3048 |
| MM) OF EACH ROOM USED FOR SLEEPING PURPOSES.(VERIFY IF |
| APPLICABLE) |
| - MODIFY AND RE-CALCULATE THE LOAD CLACS IT SEEMS YOU |
| WENT WITH THE OPTIONAL METHOD, THEREFORE WITH THE 3 VA |
| FOR THE GENERAL LIGHTING , THE 2 SMALL APPLIANCE(1500 |
| EACH) AND LAUNDRY CIRCUIT (1500), PLUS THE SUM OF THE |
| NAMEPLATE RATING OF ELECTRICAL EQUIPMENT YOUR |
| CALCULATIONS ARE UNDERSIZED THE DEMAND LOAD INCLUDING |
| THE A/C HEAT ACCORDING TO YOUR INFORMATION CAME OUT TO |
| BE 108 AMPS SO THE 100 AMP SERVICE IS INSUFFICIENT. THE |
| RISER DIAGRAM WILL ALSO HAVE TO BE RE-ADJUSTED TO |
| COMPLY WITH NEC 220.82(A)(B)(C) FEEDER AND SERVICE |
| CALCULATIONS. |
| - NEC 250.56 - SERVICE GROUNDING ELECTRODE TO BE |
| AUGMENTED BY AN ADDITIONAL ELECTRODE 6FEET AWAY OR |
| PROVIDE EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR |
| LESS. |
| - NEC 250.94 BONDING FOR OTHER SYSTEMS. THE |
| INTER-SYSTEM BONDING TERMINAL PRESCRIBED SHALL BE |
| INSTALLED. |
| |
| PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| MENTIONED DEFICIENCIES. |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| |