Plan Review Notes
Plan Review Notes For Permit 16051302
Permit Number 16051302
Review Stop G
Sequence Number 1
Notes
Date Text
2016-06-01 04:57:041) INDICATE THE TYPE OF PIPE, THE PIPE SIZE, AND THE
 LENGTH OF PIPE FROM THE STEP DOWN REGULATOR TO THE
 APPLIANCE FOR THE TANKLESS WATER HEATER, THE DRYER AND
 THE FUTURE POOL HEATER. FBC 107.2.1.
 2) SUBMIT TWO COPIES OF THE APPLICABLE PIPE SIZING
 TABLE FOR THESE APPLIANCES. FBC 107.2.1.
 3) ALL APPLIANCES SHALL BE LISTED AND LABELED PER 2014
 FGC SEC. 301.3. MANUF. INSTALLATION MANUALS FOR ALL
 APPLIANCES SHALL BE ONSITE FOR INSPECTOR.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  