Plan Review Notes For Permit 16051302 |
Permit Number |
16051302 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-06-01 04:57:04 | 1) INDICATE THE TYPE OF PIPE, THE PIPE SIZE, AND THE | | LENGTH OF PIPE FROM THE STEP DOWN REGULATOR TO THE | | APPLIANCE FOR THE TANKLESS WATER HEATER, THE DRYER AND | | THE FUTURE POOL HEATER. FBC 107.2.1. | | 2) SUBMIT TWO COPIES OF THE APPLICABLE PIPE SIZING | | TABLE FOR THESE APPLIANCES. FBC 107.2.1. | | 3) ALL APPLIANCES SHALL BE LISTED AND LABELED PER 2014 | | FGC SEC. 301.3. MANUF. INSTALLATION MANUALS FOR ALL | | APPLIANCES SHALL BE ONSITE FOR INSPECTOR. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|