 [email protected]
  
  
 PLUMBING COMMENTS:
  
 1) GREASE INTERCEPTOR'S NOT VENTED PER MANUFACTURE
 INSTALLATION SPECIFICATIONS PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 2) AUTOMATIC GREASE INTERCEPTOR IS SHOWN BELOW GRADE
 THIS MODEL IS REQUIRED TO BE MOUNTED ABOVE GRADE PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 4) 2ND REQUEST THE OCCUPANT LOAD CALCULATIONS SHOW AN
 OCCUPANT LOAD OF 153 PERSONS AND THE PLUMBING FIXTURE
 REQUIREMENTS NOTES 297 PERSONS. CLARIFY.
  
 6) 2ND REQUEST SUBMIT FACTORY SIZING CALCULATIONS FOR
 THE GREASE TRAP & GREASE INTERCEPTOR. YOU CAN CONTACT
 LEE SCHNEEWEISS WITH SCHIER AT 1-800-538-4792. 2014
 FBC-PLUMBING SEC.1003.2.
  
  
 10) 2ND REQUEST SHT. P5.1 - THE SANITARY RISER SHOWS AN
 UNVENTED SINK (SK-1) DRAINING INTO THE TOP OF THE
 INTERCEPTOR.CLARIFY.
  
  
  