 BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16051290
 ADD: 701 S. ROSEMARY AVE. SUITE : 101
 CONT: TBD/ TO BE DETERMINED
 TEL: 856-6655/ NEYITA LEIVA
 E-MAIL:
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: SAT. AUGUST 13/ 2016
 ACTION: DENIED
  
 NOTICE: NEXT REVIEW CYCLE PLEASE CORRELATE SHEETS SO
 THEY WILL BE IN ORDER SHEETS S-3.0 AND S-3.1 ARE OUT OF
 ORDER AT THE BACK OF THE PLANS!!!!!1
  
  
 1-5) COMPLIED.
  
 6A) 2ND REQUEST. THE A-8.0 SHEET HAS BEEN REVISED BUT
 THE ARCHITECTURAL SHEET FOR THIS DETAIL AND THE
 STRUCTURAL SHEETS S-3.0 FOR THE SAME ISSUES DO NOT
 MATCH THE MATERIAL TO BE INSTALLED.
 DISCREPANCY IN PLANS, 107.2.1.3. ADDITIONAL INFORMATION
 REQUIRED.
 1ST ROUND OF COMMENT. SHEET A-8.0 DETAILS SHOW THE USE
 OF STEEL TUBES IN THE HEADER AND SILL DESIGN WHERE AS
 THE STRUCTURAL SHEET S-3.0 DETAIL # 1 SHOWS THE USE OF
 A CONCRETE SILL AND CONCRETE LINTEL AND STEEL.
 DISCREPANCY IN PLANS, 107.2.1.3. ADDITIONAL INFORMATION
 REQUIRED.
  
 6B) COMPLIED.
  
 7-8) DEFERRED SUBMITTALS: 2014 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (G) ROOF TOP CURBS, PRE-ENGINEERED A/C STANDS
  
 8) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 9) 2ND REQUEST. PROVIDE ENGINEERED DETAILS FOR MOUNTING
 OACU-1 CURB TO THE ROOF STRUCTURE AND THE UNIT TO THE
 CURB. SHEET S-2.2 INDICATES DETAILS FOR OACU-1, &
 OACU-2 FOUND ON SHEET S3.1 SEE DETAIL # 1 CUT SECTION
 THAT SHOWS THE ADDITIONAL ROOF FRAMING REQUIRED. NOTE
 CURB MOUNTED CONDENSING UNITS SEE MECH. DRAWINGS. SHEET
 M7.2 CURB ROOF DETAILS. IN THE DETAIL THERE IS A
 SPECIAL NOTE. FOR BOTH THE ATTACHMENT OF THE CURB TO
 THE ROOF FRAMING AND THE UNIT TO THE CURB TO BE
 DETERMINED AND VERIFIED BY THE STRUCTURAL ENGINEER.
 ADDITIONAL ENGINEERING CALS. DATED JULY 22/ 2016 PAGES
 1-5 C & C ROOF TOP EQUIPMENT AND PAGE 6 REACTIONS DUE
 TO WIND OVERTURNING ON THE CU EQUIPMENT. THE
 CALCULATIONS FOR THE LOADS TO BE RESISTED ARE THERE BUT
 NOT THE ATTACHMENT METHOD TO RESIST THE LOADS FOR THE
 CURB TO THE ROOF FRAMING MEMBERS NOR THE ROOF TOP UNIT
 TO THE CURB!!!!!!
  
 COMMENT FROM THE 1ST REVIEW CYCLE. PROVIDE ENGINEERED
 DETAILS FOR MOUNTING OACU-1 CURB TO THE ROOF STRUCTURE
 AND THE UNIT TO THE CURB.
 2014 FBC-B 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON
 STRUCTURAL MEMBERS AND THEIR CONNECTIONS SHALL BE
 DETERMINED BY METHODS OF STRUCTURAL ANALYSIS THAT TAKE
 INTO ACCOUNT EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC
 COMPATIBILITY AND BOTH SHORT- AND LONG-TERM MATERIAL
 PROPERTIES. EVERY STRUCTURE SHALL BE DESIGNED TO RESIST
 THE OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS?
 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
  
 10) 2ND REQUEST. PLEASE INDICATE IF THIS PERMIT IS FOR
 A CHANGE OF OCCUPANCY TO AN A2 OCCUPANCY. IF SO PLANS
 ARE TO BE SUBMITTED TO P.B.C. IMPACT FEE OFFICE FOR
 IMPACT FEE ASSESSMENT.
  
 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved