| BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16051290 |
| ADD: 701 S. ROSEMARY AVE. SUITE : 101 |
| CONT: TBD/ TO BE DETERMINED |
| TEL: 856-6655/ NEYITA LEIVA |
| E-MAIL: |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: SAT. AUGUST 13/ 2016 |
| ACTION: DENIED |
| |
| NOTICE: NEXT REVIEW CYCLE PLEASE CORRELATE SHEETS SO |
| THEY WILL BE IN ORDER SHEETS S-3.0 AND S-3.1 ARE OUT OF |
| ORDER AT THE BACK OF THE PLANS!!!!!1 |
| |
| |
| 1-5) COMPLIED. |
| |
| 6A) 2ND REQUEST. THE A-8.0 SHEET HAS BEEN REVISED BUT |
| THE ARCHITECTURAL SHEET FOR THIS DETAIL AND THE |
| STRUCTURAL SHEETS S-3.0 FOR THE SAME ISSUES DO NOT |
| MATCH THE MATERIAL TO BE INSTALLED. |
| DISCREPANCY IN PLANS, 107.2.1.3. ADDITIONAL INFORMATION |
| REQUIRED. |
| 1ST ROUND OF COMMENT. SHEET A-8.0 DETAILS SHOW THE USE |
| OF STEEL TUBES IN THE HEADER AND SILL DESIGN WHERE AS |
| THE STRUCTURAL SHEET S-3.0 DETAIL # 1 SHOWS THE USE OF |
| A CONCRETE SILL AND CONCRETE LINTEL AND STEEL. |
| DISCREPANCY IN PLANS, 107.2.1.3. ADDITIONAL INFORMATION |
| REQUIRED. |
| |
| 6B) COMPLIED. |
| |
| 7-8) DEFERRED SUBMITTALS: 2014 FBC-B 1609.1.2 |
| PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE |
| 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS |
| (G) ROOF TOP CURBS, PRE-ENGINEERED A/C STANDS |
| |
| 8) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| |
| 9) 2ND REQUEST. PROVIDE ENGINEERED DETAILS FOR MOUNTING |
| OACU-1 CURB TO THE ROOF STRUCTURE AND THE UNIT TO THE |
| CURB. SHEET S-2.2 INDICATES DETAILS FOR OACU-1, & |
| OACU-2 FOUND ON SHEET S3.1 SEE DETAIL # 1 CUT SECTION |
| THAT SHOWS THE ADDITIONAL ROOF FRAMING REQUIRED. NOTE |
| CURB MOUNTED CONDENSING UNITS SEE MECH. DRAWINGS. SHEET |
| M7.2 CURB ROOF DETAILS. IN THE DETAIL THERE IS A |
| SPECIAL NOTE. FOR BOTH THE ATTACHMENT OF THE CURB TO |
| THE ROOF FRAMING AND THE UNIT TO THE CURB TO BE |
| DETERMINED AND VERIFIED BY THE STRUCTURAL ENGINEER. |
| ADDITIONAL ENGINEERING CALS. DATED JULY 22/ 2016 PAGES |
| 1-5 C & C ROOF TOP EQUIPMENT AND PAGE 6 REACTIONS DUE |
| TO WIND OVERTURNING ON THE CU EQUIPMENT. THE |
| CALCULATIONS FOR THE LOADS TO BE RESISTED ARE THERE BUT |
| NOT THE ATTACHMENT METHOD TO RESIST THE LOADS FOR THE |
| CURB TO THE ROOF FRAMING MEMBERS NOR THE ROOF TOP UNIT |
| TO THE CURB!!!!!! |
| |
| COMMENT FROM THE 1ST REVIEW CYCLE. PROVIDE ENGINEERED |
| DETAILS FOR MOUNTING OACU-1 CURB TO THE ROOF STRUCTURE |
| AND THE UNIT TO THE CURB. |
| 2014 FBC-B 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON |
| STRUCTURAL MEMBERS AND THEIR CONNECTIONS SHALL BE |
| DETERMINED BY METHODS OF STRUCTURAL ANALYSIS THAT TAKE |
| INTO ACCOUNT EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC |
| COMPATIBILITY AND BOTH SHORT- AND LONG-TERM MATERIAL |
| PROPERTIES. EVERY STRUCTURE SHALL BE DESIGNED TO RESIST |
| THE OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| LOADS? |
| 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL |
| EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO |
| WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND |
| PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 10) 2ND REQUEST. PLEASE INDICATE IF THIS PERMIT IS FOR |
| A CHANGE OF OCCUPANCY TO AN A2 OCCUPANCY. IF SO PLANS |
| ARE TO BE SUBMITTED TO P.B.C. IMPACT FEE OFFICE FOR |
| IMPACT FEE ASSESSMENT. |
| |
| 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION |
| DEVELOPMENT SERVICES DEPARTMENT |