Plan Review Notes
Plan Review Notes For Permit 16051290
Permit Number 16051290
Review Stop P
Sequence Number 1
Notes
Date Text
2016-06-21 10:49:471) SHT. AN-1.0 - CODE REFERENCES - REFERENCE IS MADE TO
 THE 2001 WPB AMENDMENTS TO FBC. REVISE TO READ 2014
 AMENDMENTS.
 2) SHT.AN-3.0 - PLUMBING FIXTURE REQUIREMENTS - REFER
 TO TABLE 403.1 OF 2014 FLORIDA PLUMBING CODE.
 3) IDENTIFY THE DIFFERENT OCCUPANCY AREAS ON THE PLAN.
 4) THE OCCUPANT LOAD CALCULATIONS SHOW AN OCCUPANT LOAD
 OF 153 PERSONS AND THE PLUMBING FIXTURE REQUIREMENTS
 NOTES 297 PERSONS. CLARIFY.
 5) THE WATER FILTRATION SYSTEM SHALL BE PROTECTED
 AGAINST CONTAMINATION PER 2014 FBC SEC.608.3.
 6) SUBMIT FACTORY SIZING CALCULATIONS FOR THE GREASE
 TRAP & GREASE INTERCEPTOR. YOU CAN CONTACT LEE
 SCHNEEWEISS WITH SCHIER AT 1-800-538-4792. 2014
 FBC-PLUMBING SEC.1003.2.
 7) IS THIS A CHANGE OF OCCUPANCY? INDICATE ON THE
 PLANS. IF SO, ADDITIONAL REVIEW COMMENTS MAY BE
 GENERATED.
 8) SHT. A-7.3 - THE ACCESSIBLE URRINAL SHALL BE MOUNTED
 WITH THE RIM LOCATED AT 17 INCHES ABOVE FINISH FLOOR,
 NOT 1'-7" AS SHOWN. 2014 FAC SEC. 605.2.
 9) GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE PER THE 2014 FAC SEC. 609.4.
 10) SHT. P5.1 - THE SANITARY RISER SHOWS AN UNVENTED
 SINK (SK-1) DRAINING INTO THE TOP OF THE
 INTERCEPTOR.CLARIFY.
 11) THE DISCHARGE OF THE INTEERCEPTORS ARE SHOWN AS
 INDIRECCT WASTES ON BOTH INTERCEPTORS. CLARIFY.ALSO,
 CLARIFY THE INLET CONNECTION TO THE AUTOMATIC GREASE
 INTERCEPTOR.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  